Selection procedure (with example), 50df modu-pac – Carrier MODU-PAC 50DF User Manual
Page 28
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Selection procedure (with example)
I Determine space requirements and design conditions.
IV Determine outdoor air ventilation rate (OAVR)
Given:
100% x cfmoa
Outdoor Air Temperature (Toa)......................95 F db, 75 F wb
OAVR =
— -
Room Design Conditions (Troom).................. 75 F db/45% rh
Room Sensible Fieat (RSH)................................. 265,000 Btuh
_ 100 x 1980
Room Latent Heat (RLH) ...................................... 60,000 Btuh
^
10,600
Ventilation Requirement (V) ............................. 0.18 cfm/sq ft
19/о о do
Moduline® variable volume systems generally supply smaller
quantities of air at lower temperatures than conventional
(manual damper or economizer),
constant volume systems. The lower temperature and
V Determine conditions of mixed air entering the
moisture content (grains/lb of air) typically results in lower
evaporator.
space relative humidity This example is based on 45% rh
Use a psychrometric chart or calculate to determine mixed
rather than the conventional 50%
air temperatures (T^adb and T^awb)
Room sensible heat and room latent heat are block load
Tmadb = 19xToa + -81xTroomdb
maximum quantities
= 79 F db
II Calculate block load grand total heat (GTH).
Btuhma = .19xBtuhoa + -81 xBtuhroom
Total Ventilation Air (outdoor air) Cfmoa
“ 19 x 38.6 +
81
x 27.2
Cfmoa = A X V
= 29 4 Btuh
"
Therefore, Ewb = 64 2 F
= i980 cim
Ventilation Total Heat (VTH)
«election.
Use psychrometric chart to determine this ventilation cooling
The grand total heat expressed in tons is
- и c
/oi u Di u \
^-ru 426,500 Btuh
VTH - 4.5 X Cfmoa X (Btuhoa “Btuhroom)
GTH - ,
q
onn Rt и
= 4 5 X 1980 X (38 6 - 27 2)
^2,000 Btu/ton
= 101,500 Btuh
= 35 6 tons
Ventilation Sensible Heat (VSH)
Unit 50DF044 (nominal 40 tons) will be the trial selection
VSH = 109 X Cfmoa x(Toadb-Troomdb)
Enter Cooling Capacities table for unit 50DF044 at 10,600
= 1.09 X 1980 X (95 - 75)
and 95° By interpolation for 64.2 F ewb, calculate that
= 43,200 Btuh
TC = 433,100 Btuh
r ,
SHC = 350,200 Btuh
Ventilation Latent Heat (VLH)
^
,
, , ,
VLH = VTH - VSH
Correctthesensibleheatcapacityforenteringdry bulbof 79F
= 101 500 - 43,200
Corr Factor = 1 09 (1 - BF) (edb - 80)
.58,300 Bfuh
:iS&)TÍ)‘^^-I0^?
ico’ ^
Heat Correction = Corr Factor x BL cfm
TSH = RSH + VSH
= ^1 05 X 10,600
= 265,000 + 43,200
= _цдзо Btuh
= 308,200 Btuh
Corrected SHC = 350,200 - 11,130
Total Latent Heat (TLH)
= 339,000 Btuh
TLH = RLH + VLH
SHC
= 60,000 + 58,300
TLDB = Evap Air db - ^ gg
= 118,300 Btuh
^
339,000
Grand Total Heat (GTH)
- 79- i
q
9 x 10 600
GTH = TSH + TLH
= A Q 7 p '
= 308,200 + 118,300
= 426 500 Btuh
design conditions, this unit will provide:
p. ,
. ui
1
1
j •
/Di t \
— 433,100 Btuh vs 426,500 Btuh required
III Determine block load air quantity
(BL
cfm).
SHC - 339,000 Btuh vs 308,200 Btuh required
If supply air temperature leaving the unit is maintained at
Latent cooling — 93,900 Btuh vs 118,300 Btuh required
Йи'ЖЖ
“•"'I’''
75 F room design is
VII Select indoor air fan speed and motor bhp. Enter Fan
1.08 X (75 - 52) = 25 Btu/cfm
Performance table for unit 50DF044. At 10,600 cfm and
_
.
.
.
system static pressure of 2.0 in. wg read by interpolation that
The following forrnula may be used to determine the maxi-
tfie standard motor is suitable. Read the fan speed required
mum block load air quantity:
(1133 rpm). Enter Indoor Air Fan Drive Data table. Select the
RSH
next higher speed pulley/belt combination (i.e 1159 rpm;
BLcfm=
25
5.3V - 5.3 motor pulley; 5-3V-8.0 fan pulley; 5 -3V -710 belts).
265 000
Select a unit that matches job electrical characteristics.
= ——
Enter Electrical Data table at unit 50DF044. Read electrical
characteristics of unit to determine power supply require-
= 10,600 cfm
ments for unit of correct nominal voltage
50DF Modu-Pac® |
#
28