60df054, Optional equipment resistances (in. wg), Heating capacities – Carrier MODU-PAC 50DF User Manual
Page 10: Пperformcince data, Cont)
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

П
ор
П
Performcince data
(cont)
COOLING CAPACITIES
60DF054
Temp (F)
Air Ent
Evap Air — Cfm/BF
18,000/ (^8~T2ao6oZo6S ] 22^000/.073
Evap Air — Ewb (F)
72
67
62
72
67
62
72
67
62
TC
686
639
596
636
648
604
704
654
612
85
SHC
361
462
565
376
485
600
392
514
612
KW
56 3
53 2
50 4
57 6
54.2
50.7
58 6
54 5
51 6
TC
650
602
558
659
610
566
666
616
572
95
SHC
347
446
546
363
472
566
380
499
572
KW
61 1
57 6
53 8
61.5
57.8
53.7
62 2
58 8
54 7
TC
629
581
538
637
589
545
644
597
552
100
SHC
340
438
538
354
465
545
371
493
552
KW
63 1
59 0
56 3
63.7
59.8
56.6
64 3
60 2
56 9
TC
608
563
518
616
570
525
622
576
532
105
SHC
333
432
518
348
457
525
365
483
532
KW
51 0
61 4
58 1
—
61 6
584
—
62 1
58 7
TC
589
540
496
597
546
502
604
552
510
110
SHC
325
423
496
344
448
502
359
475
510
KW
—
63 8
60 3
—
64.2
60.5
—
64 8
60 9
OPTIONAL EQUIPMENT RESISTANCES (in. wg)
UNIT
OPTION
UNIT CFM/TON
MODEL
Г
3
ОО
400
500
Bag Filter
14
25
38
50DF
024-
044
Economizer
03
05
08
Economizer with Exhaust
.09
.15
.23
Electric Heaters 0 5:1 (Low)
06
09
13
(Heat Cool Ratio)0 75 1 (Med)
09
15
23
1.0.1 (High)
.14
.25
.35
Bag Filter
14
25
38
Economizer
03
04
08
50DF
Economizer with Exhaust
.11
.15
.24
054
Electric Heaters 0 5:1 (Low)
12
23
38
(Heat: Cool Ratio)0 75 1 (Med)
15
30
46
1 0 1 (High)
22
39
61
Bag Filter
20
36
55
50DF
064
Economizer
04
07
11
Economizer with Exhaust
13
21
31
Electric Heaters 0 5 1 (Low)
18
35
54
(Heat Cool Ratio)0 75:1 (Med)
24
44
68
9
50DF064
HEATING CAPACITIES
Temp (F)
Air Ent
Cond
Evap Air — Cfm/BF
21,000 / .070 i 24,000 / .081
26,400 / .090
Evap Air — Ewb (F)
72
67
62
72 :
67^
62
72
67
62
TC i
796
731
669
807 ; 744
684
820
753
696
85
SHC
413
521
620
432 :
553
658
449
579
683
KW
61 9
58.8
55 9
62.4
j
59.4
56.6
63
59.9
57 1
TC
751
693
634
766;
70
Г'
649
775
714
660
95
SHC
397
505
600
418 i 536
635
433
563
657
KW
66 0
62 8
59 6
66.8'
63.4
60.4
67.2
62.7
61.1
TC
709
650
598
718
663
612
726
671
624
105
SHC
387
487
579
400
521
609
416
546
624
KW
70 3
66.6
63 4
70.9- 67.4
64.3
71 4
67 8
65 8
TC
665
609
562
672
617
576
678
624
591
115
SHC
365
471
556
384 • 502
576
399
526
591
KW
74 3
70 5
67 0
74.9
i
71.1
68.1
75 4
71 6
71 9
BF — Bypass Factor
Ewb — Entering Wet-Bulb
KW — Compr Mtr Pwr Input
NOTES;
SHC — Sensible Heat Cap
(1000 Btuh)
TC — Total Cap (1000 Btuh) Gross
Direct interpolation is permissible Do not extrapolate
The following formulas may be used.
f|db fedb
sensible capacity (Btuh)
f|wb
1 09
X
cfm
Wet-bulb temperature of corresponding to enthalpy of air leaving
evaporator coil (h|^p)
total capacity (Btuh)
h|wb = hewb------------ ------------------
Where:
hewb" Enthalpy of air entering evaporator coil
SHC is based on 80 F edb temp of air entering evaporator coil Below 80 Fedb,
subtract (corr factor x cfm) from SHC
VOLTS
(Nominal)
KW ^
STAGE
1%
BTUH
208-230
460
208-230
460
208-230
460
30-37
I
37
;
45-55
55
1
75-91
91
’50
;
50
:
67
;
67
,
60
i
60
102,390-126,280
; 126,280
1153,585-187,715
; 187,715
255,975-310.585
310,585
208-230
' 45-55
1 67
1153,585-187,715
460
i
55
^ 67
187,715
208-230
1
60-73
! 50
¡204,780-249,150
460
;
73
50
249,150
208-230
30-110
' 50
1307,170-375,430
460
i
110
: 50
375,430
208-230
1
45-55
i
67
153,585-187,715
460
55
; 67
187,715
208-230
i 75-91
! 60
255,975-310,585
460
; 91
i 60
310,585
208-230
Ì105-128
1
57
358.365-436,865
I
460
; 128
57
436,865
50DF054 ■
208-230
! 60-73
1
50
1204,780-249,150
460
i 73 ;
50
i
249,150
208-230
190-110
1
50
1307,170-375,430
460
1
110
50
! 375,430
208-230
135-165
1
56
¡460.755-563,145
460
; 165
56
: 563,145
208-230
i
75-91
1
66
255,975-310,586
460
; 91 ;
60
;■ -310,585
208-230
120-146 :
50
409,560-498,300
460
! 146
50
498,300
208-230
1
75-91
1
66
1255,975-310,585
460
i 91 ;
60
310,585
208-230
0 20-146 ,
50
¡409,560-498,300
460
; 146
50
: 498,300
BF
Entering Air Dry-Bulb Temp (F)
Correction Factor
.05
1.04
2 07
3 11
4 14
5 18
.10
98
1 96
2 94
3 92
491
.20
87
1 74
2.62
3.49
4 36
use formula
shown below
Interpolation is permissible
Correction Factor = 1.09 x (1 - BF) x (edb - 80)
4 Cooling capacities are gross and do not include deduction for indoor fan
motor heat
«
1182