Physical data i, 50df modii"pac – Carrier MODU-PAC 50DF User Manual
Page 25
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Physical data
I
50DF Modii"Pac® |
UNIT SODF
024 i
028 1
034 :
044 ^
054 i
064
OPERATING WEIGHT (ib)
i
Base Unit
3000
3700
4400
5406
6100 :
6485
Economizer
150
175
200
225
250
250
Roof Curb
125
150
175
200
225
COMPRESSOR
Serviceable, Hermetic
No. ..Type
1 06E
2 06D
2 06D
2 06E
2 06EA275,250
2 06E
No. Cylinders (ea). .Rpm
4 1750
6 1750
6 1750
4 1750
4,6 1750
6 1750
Capacity Steps (%) (Std)
50,100
19,38,57,
62,81,100
16,33,50,
63,83,100
25,50,75,
100
20,40,60,
80,100
16,33,50,
67,83,100
REFRIGERANT CHARGE
Type 22; Controlled by Thermostatic Expansion Valve
Sys 1...Sys 2 (lb)
36 —
23 75 18 25:
29 0 29 0 1 37 0 37 0 Î
53 0..42 0 '
81 .81
OUTDOOR AIR FANS
Direct Driven, Propeller Type
No. ...Diameter (in.)
2...30
2 30
3 30
3 30
4 30
4 30
Nominal Cfm
14,000
14,000
21,000
21,000
28,000
31,000
Motor Hp...Rpm
1 ..1050
1 1050
1 1050
1 1050
1 1050
1 1150
CONDENSER COIL
Rows ..Fins/in.
3 139
3 13.9
3. .15 8
3 158
3 158
4 .15
Total Face Area (sq ft)
31 1
38 0
49 0
61 0
81 5
81 25
INDOOR AIR FAN
Belt Drive, Centrifugal Type
No. ...Size (in.)
2 15x11
2 . 15x15
3 .15x9
4. .15x9
4 15x11
4 15x11
Max Allowable Rpm
1300
1300
1300
1300
1300
1450
Standard Drive* Fan Pulley Bore
1-3/16
1-3/16
1 - 1 1 / 1 6
1 - 1 1 / 1 6
1 - 1 1 / 1 6
1 - 1 1 / 1 6
Fan Pulley Pitch Diam (in.)
106
106
106
10.6
106
80
Motor Hp...Rpm
Motor Pulley Pitch Diam (in.)
t 1750
7 - 1 / 2 . 1750
1 0 . 1 7 5 0
1 5 1750
20 1750
25 1750
Pulley A
6 5
6 5
6 5
6 5
6 5
5 6
Pulley B
Resulting Fan Rpm
60
5.6
5 6
5.6
60
60
With Pulley A
1073
1073
1073
1073
1073
1225
With Pulley B
991
925
925
925
991
1 3 1 2
Optional Drive*
Fan Pulley Pitch Diam (in.)
80
80
80
80
80
60
Motor Hp...Rpm
Motor Pulley Pitch Diam (in.)
7V2 1750
10. .1750
15 1750
20 .1750
25 1750
30 1750
Pulley A
5 3
5 3
53
53
5 3
50
Pulley B
Resulting Fan Rpm
5 6
5 6
5 6
56
5 6
t
With Pulley A
1 1 5 9
1 1 5 9
1 1 5 9
1 1 5 9
1 1 5 9
1450
With Pulley B
1225
1225
1225
1225
1225
t
EXHAUST FAN MOTOR—No...Hp
1 .3
1 3
1 . 3
2 3
2 3
r
2 3
EVAPORATOR COIL
Rows...Fins/in.
4 139
4 139
4 13 9
4 139
4 139
4 139
Total Face Area (sq ft)
15 1
17 7
24 8
30 2
35 4
35 4
ELEC RESISTANCE HEATERS
Open Nichrome Wire Elements with Multiple-Stage Control
Kw
37
55
55
73
91
91
INDOOR AIR FILTERS
No. ...Size
Standard; 2-in. Throwaway
6
20x25
6 16x25
18 16x25
9 20x25
12 16x25
27 16x25
9 20x25
21 16x25
9 20x25
21. .16x25
Bag Type; 12-in. (Opt)
3 12x24
4 12x24
5 12x24
6 12x24
7 12x24
3 . 2 4 x 2 4
4 24x24
5 24x24
6 24x24
7. 24x24
*Standard fan motor supplied with standard fan drive pulleys and
belts: optional fan motor supplied with optional fan drive pulleys
and belts Other combinations are field supplied Pulley A is installed
in unit; pulley B is shipped with unit.
t208/230-volt units use standard 7 - 1 / 2 hp motors. 460-volt units
use standard 5 hp motor and optional 7 - 1 / 2 hp motor
tThe 50DF064 optional drive is supplied with pulley A installed in unit
Pulley B is not supplied
25
1182