beautypg.com

Physical data i, 50df modii"pac – Carrier MODU-PAC 50DF User Manual

Page 25

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Physical data

I

50DF Modii"Pac® |

UNIT SODF

024 i

028 1

034 :

044 ^

054 i

064

OPERATING WEIGHT (ib)

i

Base Unit

3000

3700

4400

5406

6100 :

6485

Economizer

150

175

200

225

250

250

Roof Curb

125

150

175

200

225

COMPRESSOR

Serviceable, Hermetic

No. ..Type

1 06E

2 06D

2 06D

2 06E

2 06EA275,250

2 06E

No. Cylinders (ea). .Rpm

4 1750

6 1750

6 1750

4 1750

4,6 1750

6 1750

Capacity Steps (%) (Std)

50,100

19,38,57,

62,81,100

16,33,50,

63,83,100

25,50,75,

100

20,40,60,

80,100

16,33,50,

67,83,100

REFRIGERANT CHARGE

Type 22; Controlled by Thermostatic Expansion Valve

Sys 1...Sys 2 (lb)

36 —

23 75 18 25:

29 0 29 0 1 37 0 37 0 Î

53 0..42 0 '

81 .81

OUTDOOR AIR FANS

Direct Driven, Propeller Type

No. ...Diameter (in.)

2...30

2 30

3 30

3 30

4 30

4 30

Nominal Cfm

14,000

14,000

21,000

21,000

28,000

31,000

Motor Hp...Rpm

1 ..1050

1 1050

1 1050

1 1050

1 1050

1 1150

CONDENSER COIL

Rows ..Fins/in.

3 139

3 13.9

3. .15 8

3 158

3 158

4 .15

Total Face Area (sq ft)

31 1

38 0

49 0

61 0

81 5

81 25

INDOOR AIR FAN

Belt Drive, Centrifugal Type

No. ...Size (in.)

2 15x11

2 . 15x15

3 .15x9

4. .15x9

4 15x11

4 15x11

Max Allowable Rpm

1300

1300

1300

1300

1300

1450

Standard Drive* Fan Pulley Bore

1-3/16

1-3/16

1 - 1 1 / 1 6

1 - 1 1 / 1 6

1 - 1 1 / 1 6

1 - 1 1 / 1 6

Fan Pulley Pitch Diam (in.)

106

106

106

10.6

106

80

Motor Hp...Rpm
Motor Pulley Pitch Diam (in.)

t 1750

7 - 1 / 2 . 1750

1 0 . 1 7 5 0

1 5 1750

20 1750

25 1750

Pulley A

6 5

6 5

6 5

6 5

6 5

5 6

Pulley B

Resulting Fan Rpm

60

5.6

5 6

5.6

60

60

With Pulley A

1073

1073

1073

1073

1073

1225

With Pulley B

991

925

925

925

991

1 3 1 2

Optional Drive*

Fan Pulley Pitch Diam (in.)

80

80

80

80

80

60

Motor Hp...Rpm
Motor Pulley Pitch Diam (in.)

7V2 1750

10. .1750

15 1750

20 .1750

25 1750

30 1750

Pulley A

5 3

5 3

53

53

5 3

50

Pulley B

Resulting Fan Rpm

5 6

5 6

5 6

56

5 6

t

With Pulley A

1 1 5 9

1 1 5 9

1 1 5 9

1 1 5 9

1 1 5 9

1450

With Pulley B

1225

1225

1225

1225

1225

t

EXHAUST FAN MOTOR—No...Hp

1 .3

1 3

1 . 3

2 3

2 3

r

2 3

EVAPORATOR COIL

Rows...Fins/in.

4 139

4 139

4 13 9

4 139

4 139

4 139

Total Face Area (sq ft)

15 1

17 7

24 8

30 2

35 4

35 4

ELEC RESISTANCE HEATERS

Open Nichrome Wire Elements with Multiple-Stage Control

Kw

37

55

55

73

91

91

INDOOR AIR FILTERS

No. ...Size

Standard; 2-in. Throwaway

6

20x25

6 16x25

18 16x25

9 20x25

12 16x25

27 16x25

9 20x25

21 16x25

9 20x25

21. .16x25

Bag Type; 12-in. (Opt)

3 12x24

4 12x24

5 12x24

6 12x24

7 12x24

3 . 2 4 x 2 4

4 24x24

5 24x24

6 24x24

7. 24x24

*Standard fan motor supplied with standard fan drive pulleys and

belts: optional fan motor supplied with optional fan drive pulleys
and belts Other combinations are field supplied Pulley A is installed
in unit; pulley B is shipped with unit.

t208/230-volt units use standard 7 - 1 / 2 hp motors. 460-volt units

use standard 5 hp motor and optional 7 - 1 / 2 hp motor

tThe 50DF064 optional drive is supplied with pulley A installed in unit

Pulley B is not supplied

25

1182