TROUBLESHOOTING

PROBLEM DESCRIPTION

PROBABLE ROOT CAUSE

SUGGESTED ACTION

* LCD does not show input voltage value

* AC input failure alarm active

(1 beep / 4s) however AC input source is OK

Input power cord is not connected

Check input power cord connection.

Input power cord is connected into UPS outlet.

Check input power cord connection.

UPS cannot be powered on even AC input is OK.

Beep alarm (1 beep/s) & LCD shows:

EP

EPO function is active.

Re-establish emergency power off switch
and set UPS in normal mode.

UPS cannot be powered on even AC input is OK.

ON push button is not been selected properly

Push ON button during 2 seconds or
longer

1 beep / s alarm is active and LCD shows:

Internal or external batteries are not properly
connected

Check battery connection.

* Code: 02

* 1 beep / s

Input Neutral not connected or input phase
fuse open.

Check input Neutral connection. Reset
alarm in parameter 03 on LCD. If input
phase fuse is broken replace it.

* Intermittent:

+

* 2 beeps per second.

UPS overloaded

Disconnect devices from UPS outlets until
solving overload

* Intermittent:

+

* 2 beeps per second.

* By-Pass activated

UPS overloaded. UPS has changed to BYPASS
mode to avoid internal damage.

Disconnect devices from UPS outlets until
solving overload

After repetitive small overloads, UPS has
changed to BYPASS mode.

Disconnect devices from UPS until solving
overload. Then power off UPS and re-star
it.

* Code 43

* Active:

* Continuous beep

UPS has been automatically powered off
because overload.

Disconnect devices from UPS outlets until
solving overload. Then power ON.

* Code 14, 15 or 17

* Active:

* Continuous beep

UPS has been automatically powered off
because short circuit detected at output.

Check short circuit problem in devices
connected to UPS

* Intermittent: +

3F

* 1 beep / s

Parallel communication lost.

Check parallel cables and PAR 00X text on
each LCD. If problem is solved reset alarm
with UP and DOWN simultaneous key
selection.

* Any of the error codes activated

Probable internal UPS failure.

Contact service center.

Backup time is lower than expected

Batteries are not fully charged or maybe they
are worn out.

Let UPS recharge batteries during 6 hours.
If it does not solve the problem batteries
maybe need to be replaced.