EXTERNAL BATTERY CABINETS – CONNECTION PROCEDURE

UPS Tower type

WARNING

Make sure EXBATT model to be connected is compatible with UPS model. For OPTIMA-33 models, battery pack voltage is 240Vdc.

Measure and verify DC voltage supplied by battery pack before making connections.


1.- Check all DC breakers are in OFF position

2.- Remove all DC connector covers in UPS and EXBATT cabinets

3.- Using appropriate cable (supplied with the EXBATT) connect UPS with EXBATT 1. In case of more than 1 EXBATT connect EXBATT 1 with
EXBATT 2 and so on until last EXBATT.

4.- Activate DC breakers one by one in EXBATT cabinets to connect EXBATT batteries with internal UPS Main batteries.