beautypg.com

User manual, Circuit breakers and wiring selection – XMART Optima 33 30K User Manual

Page 10

background image

USER MANUAL

- OPTIMA-33 10K / 20K / 30K

www.xmart-ups.com

130612-OPTIMA-33 10K/20K (ENGLISH) - 8

CIRCUIT BREAKERS AND WIRING SELECTION


Breakers and Gauge of the wires used in the installation must be rated to drive current values in Amps as indicated in below tables.
NOTE every country has its local electrical requirements and regulations. If local electrical regulations require higher rates than suggested values
in this section, please follow local regulations.

400/230VAC

INPUT

OUTPUT

EXT. BATT

MODEL

BREAKER & WIRING

BREAKER & WIRING

BREAKER & WIRING

10KVA

(400/230VAC)

Breaker: 32A AC (Curve D)

Max. Nominal Current (Ph-N):

- 19A in normal mode (@200V)

Wiring (min. recommended size):

* Phase: 10AWG (6 mm2)

* Neutral: 8AWG (10 mm2)

* Ground: 8AWG (10 mm2)

Breaker: 32A AC (Curve D)

Max. Nominal Current (Ph-N):

- 15A in normal mode (@220V)

Wiring (min. recommended size):

* Phase: 10AWG (6 mm2)

* Neutral: 8AWG (10 mm2)

* Ground: 8AWG (10 mm2)

Breaker: 50Amps DC (Curve C)

Wiring (min. recommended size):

* 8 AWG (10mm2)

20KVA

(400/230VAC)

Breaker: 50 Amps AC (Curve D)

Max. Nominal Current (Ph-N):

- 38A in normal mode (@200V)

Wiring (min. recommended size):

* Phase: 8 AWG (10 mm2)

* Neutral: 6 AWG (16 mm2)

* Ground: 6 AWG (16 mm2)

Breaker: 50 Amps AC (Curve D) Max.

Nominal Current (Ph-N):

- 30A in normal mode (@220V)

Wiring (min. recommended size):

* Phase: 8 AWG (10 mm2)

* Neutral: 6 AWG (16 mm2)

* Ground: 6 AWG (16 mm2)

Breaker: 100Amps DC (Curve C)

Wiring (min. recommended size):

* 6 AWG (16mm2)

30KVA

(400/230VAC)

Breaker: 63 Amps AC (Curve D)

Max. Nominal Current (Ph-N):

- 56A in normal mode (@200V)

Wiring (min. recommended size):

* Phase: 8 AWG (10 mm2)

* Neutral: 6 AWG (16 mm2)

* Ground: 6 AWG (16 mm2)

Breaker: 63 Amps AC (Curve D) Max.

Nominal Current (Ph-N):

- 45A in normal mode (@220V)

Wiring (min. recommended size):

* Phase: 8 AWG (10 mm2)

* Neutral: 6 AWG (16 mm2)

* Ground: 6 AWG (16 mm2)

Breaker: 150Amps DC (Curve C)

Wiring (min. recommended size):

* 3 AWG (35mm2)

Recommended cable size according to 1999 NEC (301-17) based on 30ºC air ambient temperature for single cable.

WARNING:

Above wiring and breakers rates are only a suggestion. The wire size is strongly affected by diverse factors such as: Operation

temperature, wire length, type of wire, quantity of conductors and kind of installation. Electrical contractor must assure an

appropriate selection for wire and protection devices sizing for complying with local regulations for electrical installations. Wiring

colors must be selected according to local directives and regulations


This manual is related to the following products: