130612-OPTIMA-33 10K/20K (ENGLISH) - 33
13: Battery voltage calibration
Interface
Setting
Parameter 2: Select “Add” or “Sub” function to adjust battery voltage to real figure.
Parameter 3: the voltage range is from 0V to 9.9V and the default value is 0V.
14: Charger voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust charger voltage
Parameter 3: the voltage range is from 0V to 9.9V and the default value is 0V.
NOTE:
*Before making voltage adjustment, be sure to disconnect all batteries first to get the
accurate charger voltage.
* Any modification should be suitable to battery specifications.
15: Inverter A voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust inverter A voltage.
Parameter 3: the voltage range is from 0V to 9.9V and the default value is 0V.
16: Inverter B voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust inverter B voltage*.
Parameter 3: the voltage range is from 0V to 9.9V and the default value is 0V.
*It will display number 1 under
or
to represent inverter B voltage.
17: Inverter C voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust inverter C voltage*.
Parameter 3: the voltage range is from 0V to 9.9V, the default value is 0V.
*It will display number 2 under
or
to represent inverter C voltage.