18: Output A voltage calibration
Interface
Setting
Parameter 2: it always shows OP.V as output voltage.
Parameter 3: it shows the internal measurement value of the output A voltage, and you
can calibrate it by pressing Up or Down according to the measurement from an external
voltage meter. The calibration result will be effective by pressing Enter. The calibration
range is limited within +/-9V. This function is normally used for parallel operation.
19: Output B voltage calibration
Interface
Setting
Parameter 2: it always shows OP.V as output voltage*.
Parameter 3: it shows the internal measurement value of the output B voltage, and you
can calibrate it by pressing Up or Down according to the measurement from an external
voltage meter. The calibration result will be effective by pressing Enter. The calibration
range is limited within +/-9V. This function is normally used for parallel operation.
*It will display number 1 under
to represent the output B voltage.
20: Output C voltage calibration
Interface
Setting
Parameter 2: it always shows OP.V as output voltage.
Parameter 3: it shows the internal measurement value of the output C voltage, and you
can calibrate it by pressing Up or Down according to the measurement from an external
voltage meter. The calibration result will be effective by pressing Enter. The calibration
range is limited within +/-9V. This function is normally used for parallel operation.
*It will display number 2 under
to represent the output C voltage.