01: Output voltage

Interface

Setting

Parameter 3: Output voltage

You may choose the following output voltage in parameter 3:
208: Presents output voltage is 208Vac

220: Presents output voltage is 220Vac

230: Presents output voltage is 230Vac

240: Presents output voltage is 240Vac

02: Output frequency

Interface

Setting

60 Hz, CVCF mode

50 Hz, Normal mode

ATO

Parameter 2: Output Frequency

Setting the output frequency. You may choose following three options in parameter 2:
50.0Hz: The output frequency is setting for 50.0Hz.

60.0Hz: The output frequency is setting for 60.0Hz.

ATO: If selected, output frequency will be decided according to the latest normal utility

frequency. If it is from 46Hz to 54Hz, the output frequency will be 50.0Hz. If it is from
56Hz to 64Hz, the output frequency will be 60.0Hz. ATO is default setting.


Parameter 3: Frequency mode

Setting output frequency at CVCF mode or not CVCF mode. You may choose following
two options in parameter 3:
CF: Setting UPS to CVCF mode. If selected, the output frequency will be fixed at 50Hz or

60Hz according to setting in parameter 2. The input frequency could be from 46Hz to
64Hz.
NCF: Setting UPS to normal mode (not CVCF mode). If selected, the output frequency

will synchronize with the input frequency within 46~54 Hz at 50Hz or within 56~64 Hz
at 60Hz according to setting in parameter 2. If 50 Hz selected in parameter 2, UPS will
transfer to battery mode when input frequency is not within 46~54 Hz. If 60Hz selected
in parameter 2, UPS will transfer to battery mode when input frequency is not within
56~64 Hz.

*If Parameter 2 is ATO, the Parameter 3 will show the current frequency.


IMPORTANT NOTES:

* If CF function is enable to generate an output frequency different to input frequency, bypass mode will be disable automatically.

However when UPS is powered on it will enter in temporary bypass mode during a couple of seconds.

* When CF function is enable, maximum output power is reduced in about 40%. It means a 10KVA UPS will offer a maximum power of

6KVA.

03: Voltage range for bypass

Interface

Setting

Parameter 2: Set the acceptable low voltage for bypass. Setting range is from 110V to

209V and the default value is 110V.
Parameter 3: Set the acceptable high voltage for bypass. Setting range is from 231V to

276V and the default value is 264V.