- OPTIMA-33 10K / 20K / 30K

www.xmart-ups.com

130612-OPTIMA-33 10K/20K (ENGLISH) - 15

6.- START-UP: SINGLE UPS


INSPECTION BEFORE START UP

1. Make sure all wires are tightly connected to terminal block. Any loose connection will produce overheating, failures and damage to

UPS.

2. Make sure all instructions of sections 3 and 4 have been performed correctly.
3. Put the terminal block cover back in its position to avoid access to wiring.
4. Check EPO connections.

• EPO Port closed (Wired): EPO function disabled
• EPO port connected to an emergency switch: EPO function available by activation of Emergency Switch; which must be

“Normally Closed” type in order to guarantee that UPS will shut down when circuit opens.

5. Check Maintenance Bypass Switch (MBS) located in UPS rear panel is in UPS position and its cover is duly installed.

6. Make sure all external protection devices in input and output lines are in open (OFF) position.

SINGLE UPS - START UP PROCEDURE

1. Make sure all equipments connected to UPS are off
2. Power AC input at electrical panel board by setting input AC Lines Circuit Breaker to ON
3. Put Battery Bank breaker to ON (Only for Ex Models, If using external battery pack)
4. Put AC INPUT Breaker to ON in UPS rear panel.
5. LCD in front panel starts to show bypass mode. UPS Outputs are powered although UPS is off because it is on By-Pass mode. At this

moment output power is being supplied by AC Input Power Line.

6. Start up the UPS by pressing On push button in front panel until beep is heard and ON message displayed on top of the LCD.
7. Few seconds after, the UPS leaves By-Pass mode to enter in Normal Online Mode, also known as “AC Mode”
8. Power on sequentially each equipment connected to UPS output. The front panel LCD should show the load increase as equipments

start.

9. Once all equipments are on, the total power consumption (load) should not exceed UPS capacity.
10. At this moment UPS working under NORMAL AC-MODE and the system is supplied by UPS.

NOTE 1: If any error or warning message in indicated in LCD please revise Troubleshooting section of this manual.
NOTE 2: UPS batteries maybe are not fully charged. UPS could require about 4 to 6 hours to recharge batteries up to 100% of their

capacity.