User manual – XMART Optima 33 30K User Manual
Page 4
USER MANUAL
- OPTIMA-33 10K / 20K / 30K
www.xmart-ups.com
130612-OPTIMA-33 10K/20K (ENGLISH) - 2
• To enlarge batteries life expectancy it is recommendable to fully discharge UPS one every 2 to 3 months
• During UPS storage recharge batteries according to the following table:
WARNING: EQUIPMENT DISPOSAL
Out of service units :
It is strongly recommended to dispose this piece of equipment according to valid directives in your
country. At the moment of disposing all pieces need to be managed appropriately to avoid possible environmental damage or for
some materials to be recycled.
Batteries :
Do not throw it to fire (risk of explosion). Do not open the batteries, there are dangerous liquids inside
WARNING: BATTERIES MAINTENANCE
• Batteries capacity, in general (of all kinds), decrease with time and use.
• Our products contain high quality batteries only.
• Batteries useful life in our UPS is between 4 and 5 years, considering environment temperature under 25 ºC and optimal
operational conditions. This time can be dramatically reduced by high temperature and other adverse operation
condition.
• Batteries life expectancy may be also affected by other operation conditions such as electrical service quality as well as
number and kind of equipments connected to UPS
• Batteries should be periodically tested to check capacity and assure and appropriate back up.
Storage Temperature
Recharging Frequency
Recharging Time
-25°C a +30°C
Every 4 months
During 6 hours
+30°C a +45°C
Every 2 months
During 6 hours
SAFETY STANDARDS
SAFETY:
IEC/EN 62040-1
EMI (Radiated):
FCC part15, Subpart B (Class A)
EMI (Radiated):
IEC/EN 62040-2 (Cat 3)
EMI (Conducted):
IEC/EN 62040-2 (Cat 3)
SURGE IMMUNITY
IEEE / ANSI C62.41 (Cat A & B)
EMS Power-Frequency Magnetic Field:
IEC/EN 61000-4-8 (Level 4)
EMS Low Freq. Signals:
IEC/EN 61000-2-2
EMS (ESD):
IEC/EN 61000-4-2 (Level 4)
EMS (RS):
IEC/EN 61000-4-3 (Level 3)
EMS (EFT):
IEC/EN 61000-4-4 (Level 4)
EMS (SURGE):
IEC/EN 61000-4-5 (Level 4)
EMS (CS):
IEC/EN 61000-4-6 (Level 3)
TRANSPORTATION:
ISTA 1A
This product has been designed to operate in industrial and commercial applications. If it is used in different application some
considerations for avoiding interferences could be necessary.