USER MANUAL

- OPTIMA-33 10K / 20K / 30K

www.xmart-ups.com

130612-OPTIMA-33 10K/20K (ENGLISH) - 31

04: Frequency range for bypass

Interface

Setting

Parameter 2: Set the acceptable low frequency for bypass.

50 Hz system: Setting range is from 46.0Hz to 49.0Hz.
60 Hz system: Setting range is from 56.0Hz to 59.0Hz.

The default value is 46.0Hz/56.0Hz.
Parameter 3: Set the acceptable high frequency for bypass.

50 Hz: Setting range is from 51.0Hz to 54.0 Hz.
60 Hz: Setting range is from 61.0Hz to 64.0Hz.
The default value is 54.0Hz/64.0Hz.

05: ECO mode enable/disable

Interface

Setting

Parameter 3: Enable or disable ECO function. You may choose following two options:

DIS: disable ECO function

ENA: enable ECO function

If ECO function is disabled, voltage range and frequency range for ECO mode still can be
set, but it is meaningless unless the ECO function is enabled.

06: Voltage range for ECO mode

Interface

Setting

Parameter 2: Low voltage point in ECO mode. The setting range is from -5% to -10% of

the nominal voltage.
Parameter 3: High voltage point in ECO mode. The setting range is from +5% to +10%

of the nominal voltage.

07: Frequency range for ECO mode

Interface

Setting

Parameter 2: Set low voltage point for ECO mode.

50 Hz system: Setting range is from 46.0Hz to 48.0Hz.
60 Hz system: Setting range is from 56.0Hz to 58.0Hz.
The default value is 48.0Hz/58.0Hz.
Parameter 3: Set high voltage point for ECO mode.

50 Hz: Setting range is from 52.0Hz to 54.0 Hz.
60 Hz: Setting range is from 62.0Hz to 64.0Hz.
The default value is 52.0Hz/62.0Hz.

08: Bypass mode setting

Interface

Setting

Parameter 2:

OPN: Bypass allowed. When selected, UPS will run at Bypass mode depending on

bypass enabled/disabled setting.
FBD: Bypass not allowed. When selected, it’s not allowed for running in Bypass mode

under any situations.
Parameter 3:

ENA: Bypass enabled. When selected, Bypass mode is activated.

DIS: Bypass disabled. When selected, automatic bypass is acceptable, but manual

bypass is not allowed. Manual bypass means users manually operate UPS for Bypass
mode. For example, pressing OFF button in AC mode to turn into Bypass mode.