User manual – XMART Optima 33 30K User Manual
Page 38
USER MANUAL
- OPTIMA-33 10K / 20K / 30K
www.xmart-ups.com
130612-OPTIMA-33 10K/20K (ENGLISH) - 36
ALARM CODES ON LCD
WARNING
CODE
WARNING
DESCRIPTION
01
Battery unconnected
02
Input Neutral loss
04
Input Phase Abnormal
07
Battery over charge
08
Low battery
09
Overload
0A
Fan failure
0B
EPO enable
0D
Over temperature
0E
Charger failure
10
L1 Input fuse broken
11
L2 Input fuse broken
12
L3 Input fuse broken
21
In parallel systems: line situation different
22
In parallel systems: bypass situation different
33
Locked in bypass after overload 3 times in 30min
34
Converter current unbalance
35
Battery fuse broken
36
Inverter inter-current unbalance
3A
Cover of maintain switch is open
3C
Utility extremely unbalanced
3D
BYPASS unstable
WARNING:
ALARMS RESET:
** Some alarms can block UPS avoiding normal operation of UPS until they are reset. Technician must revise original cause of the
reported error has been solved and then alarm must be reset by simultaneous selection of UP and DOWN keys in front panel
meanwhile UPS is in BYPASS mode (connected to AC source previous to select ON command).