User manual – XMART Optima 33 30K User Manual

Page 38

background image

USER MANUAL

- OPTIMA-33 10K / 20K / 30K

www.xmart-ups.com

130612-OPTIMA-33 10K/20K (ENGLISH) - 36


ALARM CODES ON LCD

WARNING

CODE

WARNING

DESCRIPTION

01

Battery unconnected

02

Input Neutral loss

04

Input Phase Abnormal

07

Battery over charge

08

Low battery

09

Overload

0A

Fan failure

0B

EPO enable

0D

Over temperature

0E

Charger failure

10

L1 Input fuse broken

11

L2 Input fuse broken

12

L3 Input fuse broken

21

In parallel systems: line situation different

22

In parallel systems: bypass situation different

33

Locked in bypass after overload 3 times in 30min

34

Converter current unbalance

35

Battery fuse broken

36

Inverter inter-current unbalance

3A

Cover of maintain switch is open

3C

Utility extremely unbalanced

3D

BYPASS unstable


WARNING:

ALARMS RESET:

** Some alarms can block UPS avoiding normal operation of UPS until they are reset. Technician must revise original cause of the

reported error has been solved and then alarm must be reset by simultaneous selection of UP and DOWN keys in front panel

meanwhile UPS is in BYPASS mode (connected to AC source previous to select ON command).