beautypg.com

Wilkerson ER08 User Manual

Page 7

background image

40mm & 60mm Proportional Regulator

2R210

7

Problem

Possible Reason

Solution

Display will not light up

No 24 volts power supply

Check if the wiring is connected according to
the schematic wiring diagram

Unit will not, or not correctly respond to
given setpoint

Wrong current applied ( I.e. Volt instead of
mA or mA instead of Volt

Change setpoint current or re configure the
setpoint current through the software by
changing parameter 4

Check wiring if the setpoint signal lead is
connected to the right pin within the male M12
connector ( should be pin 2)

Setpoint signal is not stable enough

Stabilize setpoint signal input

Display shows NoP.

Unit detects that required output pressure
is higher than the supplied pressure

Adjust the inlet pressure to a higher value,
preferably 0,5 bar higher than requested output
pressure

Give lower setpoint value which corresponds to
a output pressure lower than the inlet pressure

No inlet pressure at all

Connect port 1 to the supply pressure

Unit behavior is not considered normal

Faulty settings made in the parameters

Reset the unit to factory settings by using the
green key function under parameter 0

Desired pressure can not be reached

Setpoint value to low

Pre-set pressure limit has been changed
to a lower max. outlet pressure

Increase setpoint value

Change max. outlet pressure back to required
pressure by changing parameter 19

Supply pressure is to low

Increase supply pressure

Secondary side stays pressurized

Setpoint value is higher than 0,1 Volt

Pre-set pressure has been enabled to a
certain pressure

Lower your setpoint value, preferably to 0 Volts

Reset parameter 18 to 0

Display shows unrealistic value

Display maybe configured in the wrong
value ( bar instead of psi)

Check through parameter 14, if the display
value is set on either psi or bar, if necessary
change it to the required setting

Unit response time too slow or too quick

Volume behind the unit is either too big or
too small

Adjust the regulating speed of the unit through
parameter 20

Unit gives too much overshoot

Relation between volume and response
me is out of balance

Adjust response time to a higher value through
parameter 20, to achieve more accurate
behavior

Unit is adjusting/regulating constantly

Air leakage in the system behind the unit

Constant changing volume behind the unit

“Deadband “area is set too small

Resolve leakage

Unit needs to regulate to keep required pres-
sure at the same level

Try to minimize the volume changes

Enlarge deadband setting through parameter
13 in the software ( parameter 20 has to be set
to 0 before changing parameter 13)

Can not enter software through touchpad

Unit is currently working/processing

Make sure that the unit is in steady state while
activating the software

Activating time is too short

Hold the accept button for at least 3 seconds

Display indicates ‘OL’

Wiring not according to diagram (24 volt
connected on the setpoint connection pin)

Rewire so that on the setpoint connection pin
will be either 0-10v or 4-20mA

Wrong setpoint value given in relation to
programmed setpoint value acceptance

Change over setpoint value to either V or mA
or Reprogram the unit to the correct setpoint
value via parameter 4

Any other problem

Please consult factory