Back to factory setting, Set control signal, Installation – Wilkerson ER08 User Manual
Page 2
40mm & 60mm Proportional Regulator
2R210
Installation
1. Place muffler in Port 3
2. Connect the device to the Air Supply Port 1 and 2.
3. Connect Female M12 Connector on the Male Connector of
the device.
4. Apply 24V = (10 second time delay for initialization of
unit).
5. Air Supply to Port 1.
6. Give desired Set Point Signal.
7. Secondary Pressure will now be displayed.
How to Change Parameters
Pressing the Accept key for 3 to 6 seconds, will activate parameter
change mode. The user can then select the parameters by pressing
up or down key (display will show Pxx). When parameter number is
correct, pressing accept again will enter parameter number (display
will show parameter value).
2
Back to Factory Setting
After start up. (Power is on)
Parameter 0 = 3
Entering this value in parameter 0 will store the calibrated factory data into the working parameters. (Default calibration data is
used)
Parameter Number 0 – Reset Back to Factory Settings
Step
1
2
3
4
5
Press
3-6 seconds
Until
Display
Reads
Flashing Decimal
Flashing Decimal
Flashing
Description
Accesses
changeable
parameters.
Accesses
parameter no. 0.
Displays current
parameter value.
Edits parameter.
3 = standard
factory settings. If
other than 3, use
Up or Down
Arrow and accept 3
Accepts and saves
new parameter
setting.
Sequences to next
parameter.
or
or
Set Control Signal
The unit is factory set for 0-10 V control signal. If 4-20 mA control signal is required, change parameter 4.
Parameter Number 4 – Set Control Signal in Volts or Milliamps
Step
1
2
3
4
5
Press
3-6 seconds
Until
Display
Reads
Flashing Decimal
Flashing Decimal
Flashing
Description
Accesses
changeable
parameters.
Accesses
parameter no. 4.
Displays current
parameter value.
1 = V, 0 = mA
Edits parameter.
Accepts and saves
new parameter
setting.
Sequences to next
parameter.
or
or
Pressing the up or down key will change the parameter itself
(display will flash indicating parameter editing mode). Pressing
the accept key will accept the new parameter value (all digits will
flash while being accepted).
After releasing all keys, the next parameter number will be
presented on the display (you may step to the next parameter).
When no key is pressed, after 3 seconds the display will show
the actual output pressure.
Only parameter numbers 0, 4, 9, 14, 18, 19, 20, 12, 13, and 21
are accessible to edit. All other parameters are fixed.
Manual Mode
When keys DOWN and UP are pressed during startup,
(connecting to the 24 V power supply) manual mode is activated.
This means that the user is able to in/decrease the output
pressure of the regulator, by pressing the UP or DOWN key.
During this action the display will blink, indicating that the manual
mode is activated.