beautypg.com

Back to factory setting, Set control signal, Installation – Wilkerson ER08 User Manual

Page 2

background image

40mm & 60mm Proportional Regulator

2R210

Installation

1. Place muffler in Port 3

2. Connect the device to the Air Supply Port 1 and 2.

3. Connect Female M12 Connector on the Male Connector of

the device.

4. Apply 24V = (10 second time delay for initialization of

unit).

5. Air Supply to Port 1.

6. Give desired Set Point Signal.

7. Secondary Pressure will now be displayed.

How to Change Parameters

Pressing the Accept key for 3 to 6 seconds, will activate parameter
change mode. The user can then select the parameters by pressing
up or down key (display will show Pxx). When parameter number is
correct, pressing accept again will enter parameter number (display
will show parameter value).

2

Back to Factory Setting

After start up. (Power is on)

Parameter 0 = 3

Entering this value in parameter 0 will store the calibrated factory data into the working parameters. (Default calibration data is
used)

Parameter Number 0 – Reset Back to Factory Settings

Step

1

2

3

4

5

Press

3-6 seconds

Until

Display

Reads

Flashing Decimal

Flashing Decimal

Flashing

Description

Accesses

changeable

parameters.

Accesses

parameter no. 0.

Displays current

parameter value.

Edits parameter.

3 = standard

factory settings. If

other than 3, use

Up or Down

Arrow and accept 3

Accepts and saves

new parameter

setting.

Sequences to next

parameter.

or

or

Set Control Signal

The unit is factory set for 0-10 V control signal. If 4-20 mA control signal is required, change parameter 4.

Parameter Number 4 – Set Control Signal in Volts or Milliamps

Step

1

2

3

4

5

Press

3-6 seconds

Until

Display

Reads

Flashing Decimal

Flashing Decimal

Flashing

Description

Accesses

changeable

parameters.

Accesses

parameter no. 4.

Displays current

parameter value.

1 = V, 0 = mA

Edits parameter.

Accepts and saves

new parameter

setting.

Sequences to next

parameter.

or

or

Pressing the up or down key will change the parameter itself
(display will flash indicating parameter editing mode). Pressing
the accept key will accept the new parameter value (all digits will
flash while being accepted).

After releasing all keys, the next parameter number will be
presented on the display (you may step to the next parameter).
When no key is pressed, after 3 seconds the display will show
the actual output pressure.

Only parameter numbers 0, 4, 9, 14, 18, 19, 20, 12, 13, and 21
are accessible to edit. All other parameters are fixed.

Manual Mode

When keys DOWN and UP are pressed during startup,
(connecting to the 24 V power supply) manual mode is activated.
This means that the user is able to in/decrease the output
pressure of the regulator, by pressing the UP or DOWN key.
During this action the display will blink, indicating that the manual
mode is activated.