Set deadband, Proportional effect – Wilkerson ER08 User Manual
Page 6
Parameter Number 39 – Displays Current Software Version
Step
1
2
3
Press
3-6 seconds
Until
Display
Reads
Flashing Decimal
Description
Accesses
changeable
parameters.
Accesses
parameter no. 39.
Displays current
parameter value.
XXX = current
software version
40mm & 60mm Proportional Regulator
2R210
6
Set Deadband
Deadband is the minimum limit of accuracy at which the regulator is set for normal operation. The displayed value is X 10 mbar
and has a range between 4 (40 mbar) and 40 (400 mbar).
Parameter Number 13 – Set Deadband (P20 Must be Set to 0)
Step
1
2
3
4
5
Press
3-6 seconds
Until
Display
Reads
Flashing Decimal
Flashing Decimal
(value between
4 and 40)
Flashing
Description
Accesses
changeable
parameters.
Accesses
parameter no. 13.
Displays current
parameter value.
Incremental
value is
x 10 mbar
Edits parameter.
Accepts and saves
new parameter
setting.
Sequences to next
parameter.
or
or
or
Parameter Number 21 – Set Proportional Effect (P20 Must be Set to 0)
Step
1
2
3
4
5
Press
3-6 seconds
Until
Display
Reads
Flashing Decimal
Flashing Decimal
(value between
5 and 100)
Flashing
Description
Accesses
changeable
parameters.
Accesses
parameter no. 21.
Displays current
parameter value.
Edits parameter.
5 = fastest
regulation
100 = slowest
regulation.
Accepts and saves
new parameter
setting.
Sequences to next
parameter.
Proportional Effect
Sets the speed at which the regulator adjusts either filling or exhausting. The displayed value has a range between 5 (fastest
regulation) and 100 (slowest regulation).
or
or