Objects Supported By Model
Room Temperature, Outdoor Temperature and Room Humidity need to have their Boolean override counterpart object set to “Override” first if the present
value needs to be written over from the network. Ex To set a network present value on the numeric “{Room Temperature” numeric object, the “
Room
Temperature Override”
Boolean object needs to be set from Normal to Override. The controller local present value will then be derived from the wireless
network instead of the present value at the controller.
VT7200 & VT7300 Series
Object Name
Object Type
Ob
ject Pro
p
erty
(Read/Write)
VT
7200
C5
x00
W
VT
7200F
5
x0
0
W
VT
7300
A5
x00
W
VT
7305
A5
x00
W
VT
7300
C5
x00
W
VT
7305
C5
x00
W
VT
7350
C5
x00
W
VT
7355
C5
x00
W
VT
7300F
5
x0
0
W
VT
7305F
5
x0
0
W
VT
7350F
5
x0
0
W
VT
7355F
5
x0
0
W
Room Temperature
Numeric Writable
Present Value (R,W)
Room Temperature Override
Boolean Writable Present
Value
(R,W)
Return Air Temperature
Numeric Point
Present Value (R)
Outdoor Temperature
Numeric Writable Present
Value
(R,W)
Outdoor Temperature
Override
Boolean Writable
Present Value (R,W)
Supply Temperature
Numeric Point
Present Value (R)
Room Humidity
Numeric Writable
Present Value (R,W)
Room Humidity Override
Boolean Writable
Present Value (R,W)
Occupancy Command
Enum Writable Present
Value
(R,W)
Effective Occupancy
Enum Point
Present Value (R)
Occupied Cooling Setpoint
Numeric Writable
Present Value (R,W)
Occupied Heating Setpoint
Numeric Writable
Present Value (R,W)
Stand-by Cooling Setpoint
Numeric Writable
Present Value (R,W)
Stand-by Heating Setpoint
Numeric Writable
Present Value (R,W)
Unoccupied Cooling
Setpoint
Numeric Writable
Present Value (R,W)
Unoccupied Heating
Setpoint
Numeric Writable
Present Value (R,W)
PI Cooling Demand
Numeric Point
Present Value (R)