Objects Supported By Model

Room Temperature, Outdoor Temperature and Room Humidity need to have their Boolean override counterpart object set to “Override” first if the present
value needs to be written over from the network. Ex To set a network present value on the numeric “{Room Temperature” numeric object, the “

Room

Temperature Override”

Boolean object needs to be set from Normal to Override. The controller local present value will then be derived from the wireless

network instead of the present value at the controller.



VT7200 & VT7300 Series

Object Name

Object Type

Ob

ject Pro

p

erty

(Read/Write)

VT

7200

C5

x00

W

VT

7200F

5

x0

0

W

VT

7300

A5

x00

W

VT

7305

A5

x00

W

VT

7300

C5

x00

W

VT

7305

C5

x00

W

VT

7350

C5

x00

W

VT

7355

C5

x00

W

VT

7300F

5

x0

0

W

VT

7305F

5

x0

0

W

VT

7350F

5

x0

0

W

VT

7355F

5

x0

0

W

Room Temperature

Numeric Writable

Present Value (R,W)

























Room Temperature Override

Boolean Writable Present

Value

(R,W)

























Return Air Temperature

Numeric Point

Present Value (R)

Outdoor Temperature

Numeric Writable Present

Value

(R,W)

























Outdoor Temperature

Override

Boolean Writable

Present Value (R,W)

























Supply Temperature

Numeric Point

Present Value (R)

























Room Humidity

Numeric Writable

Present Value (R,W)









Room Humidity Override

Boolean Writable

Present Value (R,W)









Occupancy Command

Enum Writable Present

Value

(R,W)

























Effective Occupancy

Enum Point

Present Value (R)

























Occupied Cooling Setpoint

Numeric Writable

Present Value (R,W)

























Occupied Heating Setpoint

Numeric Writable

Present Value (R,W)

























Stand-by Cooling Setpoint

Numeric Writable

Present Value (R,W)

























Stand-by Heating Setpoint

Numeric Writable

Present Value (R,W)

























Unoccupied Cooling

Setpoint

Numeric Writable

Present Value (R,W)

























Unoccupied Heating

Setpoint

Numeric Writable

Present Value (R,W)

























PI Cooling Demand

Numeric Point

Present Value (R)























