Viconics VWG-50 (Classic ZigBee) BACnet Integration Manual User Manual

Page 24

background image

24

Object Name

Object Type

Object Property

(Read/Write)

Controller Range / Indexes

Wireless Door Switch Status

BV

Present Value (R)

falseText=Off,trueText=On

Room Temperature Override

BV

Present Value (R,W)

falseText=Normal,trueText=Override

Outdoor Temperature Override

BV

Present Value (R,W)

falseText=Normal,trueText=Override

Room Humidity Override

BV

Present Value (R,W)

falseText=Normal,trueText=Override

Aux Command

BV

Present Value (R,W)

falseText=Off,trueText=On

Dehumidification Lockout

BV

Present Value (R,W)

falseText=Disabled,trueText=Enabled

Pulsed Heat

BV

Present Value (R,W)

falseText=Off,trueText=On



* This object is linked to UI3 input on all VT7200 and VT7300 series controller when used in binary mode. The Not
Activated / Activated flag status is changed upon a local contact closing on the input and will also result in the
SupplyTemp AV to respond from one end of its range to the other.