Viconics VWG-50 (Classic ZigBee) BACnet Integration Manual User Manual
Page 15
15
Object Name
Object Type
Ob
ject Pro
p
erty
(Read/Write)
Da
ta
Ty
pe
VZ
7200F
5
x0
0
W
VZ
7260F
5
x0
0
W
VZ
7260
C5
x00
W
VZ
7656
B1
000
W
VZ
7656
R1
000
W
VZ
7656
H1
000
W
VZ
7656F
1
00
0
W
VZ
7656E
10
00
W
Highest PI Heat Zone Mac
Numeric Point
Present Value (R)
AV
Highest PI Cool Zone Mac
Numeric Point
Present Value (R)
AV
Highest PI Heat Demand
Numeric Point
Present Value (R)
AV
Highest PI Cool Demand
Numeric Point
Present Value (R)
AV
Y1 Status
Boolean Point
Present Value (R)
BV
Y2 Status
Boolean Point
Present Value (R)
BV
Set Clock Alarm
Boolean Point
Present Value (R)
BV
Service Alarm
Boolean Point
Present Value (R)
BV
Filter Alarm
Boolean Point
Present Value (R)
BV
Discharge Temperature Alarm
Boolean Point
Present Value (R)
BV
G Fan Status
Boolean Point
Present Value (R)
BV
Keypad Lockout
Enum Writable
Present Value
(R,W)
MV
Static Pressure
Numeric Point
Present Value (R)
AV
Static Pressure Setpoint
Numeric Writable
Present Value
(R,W)
AV
Transferred Zone PI Heat Demand
Numeric Point
Present Value (R)
AV
Transferred Zone PI Cool Demand
Numeric Point
Present Value (R)
AV
Zone Comm Lost Alarm
Boolean Point
Present Value (R)
BV
RTC Zone Sequence
Enum Point
Present Value (R)
MV
Get From
Numeric Writable
Present Value
(R,W)
AV
BI1 Status
Boolean Point
Present Value (R)
BV
Aux Status
Boolean Point
Present Value (R)
BV
W1 Status
Boolean Point
Present Value (R)
BV
W2 Status
Boolean Point
Present Value (R)
BV
System Mode RTU Zoning
Enum Writable
Present Value
(R,W)
MV
Heat Stages Lockout Status
Boolean Point
Present Value (R)
BV