21


Standard Object Types Supported

Object Type

Supported

Objects

Dynamically

Creatable

Dynamically

Deletable

Optional

Properties
Supported

Writable

Properties **

Device

Max_Master

Max_Info_frames

Object_Identifier

Object_name

Max_Master

Analog Value

Reliability

Units

Present_Value

Out_of_Service

Object_Name

c

Binary Value

Reliability

Active_Text

Inactive_Text

Present_Value

Out_of_Service

Multi-state Value

Reliability

States_Text

Present_Value

Out_of_Service


** The present value of an object can only be written if identified so in the object table above.

Present_Value (R), object is read only

Present_Value (R,W), object is read / write

List of Property Analog Value Range Restrictions

Object Name

Object

Type

Object Property

(Read/Write)

Controller Range / Indexes

Return Air Temperature

AV

Present Value (R)

temperature,min=-40,max=122

Supply Temperature

AV

Present Value (R)

temperature,min=-40,max=122

Supply Temperature

AV

Present Value (R)

temperature,min=-40,max=150

Supply RH

AV

Present Value (R)

percent,min=0,max=100

PI Cooling Demand

AV

Present Value (R)

percent,min-0,max=100

PI Heating Demand

AV

Present Value (R)

percent,min-0,max=100

Weighted PI Cooling

Demand

AV

Present Value (R)

percent,min-0,max=100

Weighted PI Heating

Demand

AV

Present Value (R)

percent,min-0,max=100

Highest PI Heat Zone Mac

AV

Present Value (R)

N/A

Highest PI Cool Zone Mac

AV

Present Value (R)

N/A

Highest PI Heat Demand

AV

Present Value (R)

N/A

Highest PI Cool Demand

AV

Present Value (R)

N/A

Humidifier Output

AV

Present Value (R)

percent,min=0,max=100

Economizer Output

AV

Present Value (R)

percent,min=0,max=100

Effective Humidification RH

Setpoint

AV

Present Value (R)

percent,min=0,max=100

Controller Model Number

AV

Present Value (R)

Byte = Model Number

Module Firmware Version

Number

AV

Present Value (R)

2 Byte = Module Firrware Rev

Controller Firmware

Version Number

AV

Present Value (R)

Byte = Stat Firrware Rev

AO2 Status

AV

Present Value (R)

percent,min=0,max=100

Static Pressure

AV

Present Value (R)

pascal,min=0,max=5000