Viconics VWG-50 (Classic ZigBee) BACnet Integration Manual User Manual

Page 22

background image

22

Object Name

Object Type

Object Property

(Read/Write)

Controller Range / Indexes

By-Pass Damper Position

AV

Present Value (R)

percent,min=0,max=100

Damper Position

AV

Present Value (R)

percent,min=0,max=100

Room Temperature

AV

Present Value (R,W)

temperature,min=-40,max=122

Outdoor Temperature

AV

Present Value (R,W)

temperature,min=-40,max=122

Room Humidity

AV

Present Value (R,W)

percent,min=0,max=100

Room Humidity

AV

Present Value (R,W)

percent,min=5,max=90

Occupied Cooling Setpoint

AV

Present Value (R,W)

temperature,min=54,max=100

Occupied Heating Setpoint

AV

Present Value (R,W)

temperature,min=40,max=90

Stand-by Cooling Setpoint

AV

Present Value (R,W)

temperature,min=54,max=100

Stand-by Heating Setpoint

AV

Present Value (R,W)

temperature,min=40,max=90

Unoccupied Cooling

Setpoint

AV

Present Value (R,W)

temperature,min=54,max=100

Unoccupied Heating

Setpoint

AV

Present Value (R,W)

temperature,min=40,max=90

Heating Demand Limit

AV

Present Value (R,W)

percent,min=0,max=100

Cooling Demand Limit

AV

Present Value (R,W)

percent,min=0,max=100

Dehumidification RH

Setpoint

AV

Present Value (R,W)

percent,min=15,max=95

Dehumidification RH

Setpoint

AV

Present Value (R,W)

percent,min=30,max=95

Humidification RH Setpoint

AV

Present Value (R,W)

percent,min=10,max=90

Humidification High Limit

Setpoint

AV

Present Value (R,W)

percent,min=50,max=90

Password AV

Present Value (R,W)

none,min=0,max=1000

Static Pressure Setpoint

AV

Present Value (R,W)

pascal,min=0,max=5000

Get From

AV

Present Value (R,W)

none,min=0,max=254

Heartbeat Delay ***

AV

Present Value (R)

TRSS AV

Present Value (R)

percent,min=0,max=100

CRSS AV

Present Value (R)

percent,min=0,max=100


Room Temperature, Outdoor Temperature and Room Humidity need to have their Boolean override counterpart
object set to “Override” first if the present value needs to be written over from the network. Ex To set a network
present value on the numeric “{Room Temperature” numeric object, the “Room Temperature Override” Boolean object
needs to be set from Normal to Override. The controller local present value will then be derived from the wireless
network instead of the present value at the controller.



*** The heartbeat delay object represents the total amount of time a single controller has not updated its mandatory 3
minutes heartbeat update to the VWG. If the VWG does not receive a heartbeat update from an individual controller,
this object present value will increment from 0 to 3000 minutes by 3 minutes increment every 3 minutes. As soon as
the controller comes back online to the VWG and update its mandatory heartbeat, this object’s present value will
revert back to 0 minutes.