List of Property Enumeration Sets for BV Objects
Object Name
Object Type
Object Property
(Read/Write)
Controller Range / Indexes
Y1 Status
BV
Present Value (R) falseText=Off,trueText=On
Y2 Status
BV
Present Value (R)
falseText=Off,trueText=On
W1 Status
BV
Present Value (R)
falseText=Off,trueText=On
W2 Status
BV
Present Value (R)
falseText=Off,trueText=On
Frost Alarm
BV
Present Value (R)
falseText=Off,trueText=On
Set Clock Alarm
BV
Present Value (R)
falseText=Off,trueText=On
Service Alarm
BV
Present Value (R)
falseText=Off,trueText=On
Filter Alarm
BV
Present Value (R)
falseText=Off,trueText=On
Fan Lock Alarm
BV
Present Value (R)
falseText=Off,trueText=On
Fan Lock Alarm
BV
Present Value (R)
falseText=Off,trueText=On
Window Alarm
BV
Present Value (R)
falseText=Off,trueText=On
Discharge Temperature Alarm
BV
Present Value (R)
falseText=Off,trueText=On
Low Battery Alarm
BV
Present Value (R)
falseText=Off,trueText=On
Aux Status
BV
Present Value (R)
falseText=Off,trueText=On
DI Status
BV
Present Value (R)
falseText=Deactivated,trueText=Activated
DI1 Status
BV
Present Value (R)
falseText=Deactivated,trueText=Activated
DI2 Status
BV
Present Value (R)
falseText=Deactivated,trueText=Activated
BI1 Status
BV
Present Value (R)
falseText=Deactivated,trueText=Activated
BI2 Status
BV
Present Value (R)
falseText=Deactivated,trueText=Activated
UI3 Status
BV
Present Value (R)
falseText=Deactivated,trueText=Activated
RUI1 Status
BV
Present Value (R)
temperature,min=-40,max=122
RBI2 Status
BV
Present Value (R)
falseText=Off,trueText=On
Dehumidification Status
BV
Present Value (R)
falseText=Off,trueText=On
Dehumidification Status
BV
Present Value (R)
falseText=Off,trueText=On
G Fan Status
BV
Present Value (R)
falseText=Off,trueText=On
Reversing Valve Status
BV
Present Value (R)
falseText=Off,trueText=On
Aux Status
BV
Present Value (R)
falseText=Off,trueText=On
PIR Motion Status
BV
Present Value (R)
falseText=No Motion,trueText=Motion
PIR Motion Status
BV
Present Value (R)
falseText=No Motion,trueText=Motion
Heat Stages Lockout Status
BV
Present Value (R)
falseText=Off,trueText=On
Cool Stages Lockout Status
BV
Present Value (R)
falseText=Off,trueText=On
BO5 Status
BV
Present Value (R)
falseText=Off,trueText=On
AO2 Lock Status
BV
Present Value (R)
falseText=Inactive,trueText=Active
BO5 Lock Status
BV
Present Value (R)
falseText=Inactive,trueText=Active
Zone Comm Lost Alarm
BV
Present Value (R)
falseText=Off,trueText=On
RTC Smart Recovery Active
BV
Present Value (R)
falseText=Off,trueText=Active
Heating Valve Status
BV
Present Value (R)
falseText=Off,trueText=On
Cooling Valve Status
BV
Present Value (R)
falseText=Off,trueText=On
Wireless Window Switch Used
BV
Present Value (R)
falseText=Not Used,trueText=Used
Wireless Window Switch
Status
BV
Present Value (R)
falseText=Off,trueText=On
Wireless Door Switch Used
BV
Present Value (R)
falseText=Not Used,trueText=Used