Object

Index

Range Restrictions

Sequence Of Operation ( VT73xx & VT72xx ) Note 2

1 Cooling

only

2 Heating

only

3

Cooling & reheat

4

Heating & reheat

5

Cooling & heating 4 pipes

6

Cooling heating 4 pipes & reheat

Sequence Of Operation (VTR73xx) Note 3

1 Cooling

only

2 Heating

only

3

Cooling / Heating or Cooling With Electric Reheat

4

Heating With Electric Reheat

5

Electric Reheat Only

System Mode – VZ72xx, VT72xx & VT73xx

Note 1, Note 2 & Note 3

1 Off
2 Auto



Note 1 For VT72xx, VT73xx & VTR73xx devices, usable enumerations for the System Mode depends on Sequence of
Operation selected. The Auto mode can be used only if the AutoMode configuration parameter is set to On.

Note 2 For VT72xx & VT73xx, the default value of System Mode depends on the Local Sequence of Operation
selected and the value of the AutoMode configuration parameter.

Note 3 For VTR73xx, the default value of System Mode depends on the Local Sequence of Operation selected and
the value of the AutoMode configuration parameter.
Note 4:

VT7200 do not have fan outputs and fan mode commands

VT7300 fan mode input is dependent on local Fan Configuration

VT7600 fan mode inputs accepted are: Auto and On. All other modes are rejected.


Available Fan modes for the VT73xx & VTR73xx controller is dependent on the local configuration of the Fan Menu
parameter

Sequence of Operation

Default and Available System Mode

1 Cooling Only Cool: Cool-Off
2 Cooling with Reheat

Heat: Heat-Off-Cool-Auto **

3 Heating Only

Heat: Heat-Off

4 Heating with Reheat

Heat: Heat-Off

5 Cooling/Heating 4 Pipes

Heat: Heat-Off-Cool-Auto **

6 Cooling/Heating 4 Pipes with Reheat Heat: Heat-Off-Cool-Auto **

** The Auto mode will be available only if the AutoMode configuration parameter is set to On.

VT7200 do not have fan outputs and fan mode commands

VT7300 fan mode input is dependent on local Fan Configuration

VT7600 fan mode input accepted are: Auto and On. All other modes are rejected.