Viconics VWG-50 (Classic ZigBee) BACnet Integration Manual User Manual
Page 26
26
Object
Index
Range Restrictions
Sequence Of Operation ( VT73xx & VT72xx ) Note 2
1 Cooling
only
2 Heating
only
3
Cooling & reheat
4
Heating & reheat
5
Cooling & heating 4 pipes
6
Cooling heating 4 pipes & reheat
Sequence Of Operation (VTR73xx) Note 3
1 Cooling
only
2 Heating
only
3
Cooling / Heating or Cooling With Electric Reheat
4
Heating With Electric Reheat
5
Electric Reheat Only
System Mode – VZ72xx, VT72xx & VT73xx
Note 1, Note 2 & Note 3
1 Off
2 Auto
Note 1 For VT72xx, VT73xx & VTR73xx devices, usable enumerations for the System Mode depends on Sequence of
Operation selected. The Auto mode can be used only if the AutoMode configuration parameter is set to On.
Note 2 For VT72xx & VT73xx, the default value of System Mode depends on the Local Sequence of Operation
selected and the value of the AutoMode configuration parameter.
Note 3 For VTR73xx, the default value of System Mode depends on the Local Sequence of Operation selected and
the value of the AutoMode configuration parameter.
Note 4:
VT7200 do not have fan outputs and fan mode commands
VT7300 fan mode input is dependent on local Fan Configuration
VT7600 fan mode inputs accepted are: Auto and On. All other modes are rejected.
Available Fan modes for the VT73xx & VTR73xx controller is dependent on the local configuration of the Fan Menu
parameter
Sequence of Operation
Default and Available System Mode
1 Cooling Only Cool: Cool-Off
2 Cooling with Reheat
Heat: Heat-Off-Cool-Auto **
3 Heating Only
Heat: Heat-Off
4 Heating with Reheat
Heat: Heat-Off
5 Cooling/Heating 4 Pipes
Heat: Heat-Off-Cool-Auto **
6 Cooling/Heating 4 Pipes with Reheat Heat: Heat-Off-Cool-Auto **
** The Auto mode will be available only if the AutoMode configuration parameter is set to On.
VT7200 do not have fan outputs and fan mode commands
VT7300 fan mode input is dependent on local Fan Configuration
VT7600 fan mode input accepted are: Auto and On. All other modes are rejected.