Objects Table


Device object properties supported

Object Property

VWG Parameter

Object_Identifier
Property 75 (R)

Unique ID number of a device on a network

Object_Name
Property 77 (R,W)

Unique name of a Device on a network

Model Name
Property 70 (R)

VWG Model number

Location
Property 58 (R,W)

Default value is: Unknown

Description
Property 28 (R,W)

Default value is: Viconics Wireless Gateway

Firmware Revision
Property 44 (R)

Current BACnet firmware revision used by the VWG

Protocol Version
Property 98 (R)

Current BACnet firmware protocol version
Default is Version 1

Protocol Revision
Property 139 (R)

Current BACnet firmware protocol revision
Default is Revision 4

Max ADPU Length
Property 62 (R)

Maximum ADPU Length accepted
Default is 480

ADPU Timeout
Property 10 (R)

ADPU timeout value
Default is 3000 ms

Max_Master
Property 64 (R)

Maximum MAC address the device will poll for master on the MS-TP
network. 0 to 127, default is 127

Max_Info_Frame
Property 63 (R)

Maximum number of frames allowed in one token by the VWG, default is
20

Local Time
Property 57 (R,W)

VWG local time

Local Date (R,W)
Property 58 (R,W)

VWG local date