30 | VZ7656E1000W Installation Guide

Economizer Mode, CO

2

Level Control and Fresh Air Measurement Station



If the fresh air damper is to be used for both free cooling and CO

2

level control with a fresh

air measurement station, only the Min FA, Max FA, Min CO

2

and Max CO

2

parameters as

well as the free cooling sequence will be active.

-

The FA Range parameter should be set to something other than 0 CFM.

-

Use an air flow transmitter to read fresh air level with AI2 input (0-5 VDC
input)

-

Min FA, Max FA, Min CO

2

and Max CO

2

parameters should be set according

to the required setting.

T

HE HIGHEST VALUE BETWEEN FREE COOLING DEMAND OUTPUT AND INTERPOLATION OUTPUT

FOR THE FRESH AIR SETPOINT BASED ON THE

CO2

LEVEL WILL BE THE OUTPUT TO THE FRESH

AIR DAMPER

Min FA

Setpoint

Max FA

Setpoint

Min CO

2

Max CO

2

Current

FA Setpoint

Current CO

2

Level