24 | VZ7656E1000W Installation Guide
Prog rec
Progressive recovery enabled
Default value = Off
Progressive recovery is
automatically disabled if BI 1
is configured remote NSB
Off, = no progressive recovery.
The programmed occupied schedule time is the time at
which the system will restart and send the occupied status
to the attached zones.
On, = progressive recovery active.
The programmed occupied schedule time is the time at
which the desired occupied temperature setpoints will be
attained at the Zones. The RTU controller will
automatically optimize the equipment start time.
Occ CL
Return air sensor network
lost occupied heating
setpoint
Default: 72°F
If network communication is lost with the zone controllers,
the return air sensor will control the RTC to maintain this
setpoint.
40 to 90°F (4.5°C to 32°C)
(increments: 0.5° or 5°)
Occ HT
Return air sensor network lost
occupied heating setpoint
Default: 72°F
If network communication is lost with the zone controllers,
the return air sensor will control the RTC to maintain this
setpoint.
40 to 90°F (4.5°C to 32°C)
(increments: 0.5° or 5°)
Unocc CL
Return air sensor network lost
unoccupied cooling setpoint
Default: 82°F
If network communication is lost with the zone controllers,
the return air sensor will control the RTC to maintain this
setpoint.
54 to 100°F (12°C to 37.5°C)
(increments: 0.5° or 5°)
Unocc HT
Return air sensor network lost
unoccupied heating setpoint
Default: 65°F
If network communication is lost with the zone controllers,
the return air sensor will control the RTC to maintain this
setpoint.
40 to 90°F (4.5°C to 32°C)
(increments: 0.5° or 5°)
Sp range
Static Pressure sensor range
Default: 0
Static pressure transducer range. Voltage input range is 0
to 5 VDC.
0 = 0 to 1.5 in WC
1 = 0 to 2 in WC
2 = 0 to 3 in WC
3 = 0 to 4 in WC
4 = 0 to 5 in WC