24 | VZ7656E1000W Installation Guide

Prog rec

Progressive recovery enabled

Default value = Off

Progressive recovery is
automatically disabled if BI 1
is configured remote NSB

Off, = no progressive recovery.

The programmed occupied schedule time is the time at

which the system will restart and send the occupied status

to the attached zones.

On, = progressive recovery active.

The programmed occupied schedule time is the time at
which the desired occupied temperature setpoints will be
attained at the Zones. The RTU controller will
automatically optimize the equipment start time.

Occ CL

Return air sensor network

lost occupied heating

setpoint

Default: 72°F

If network communication is lost with the zone controllers,

the return air sensor will control the RTC to maintain this

setpoint.

40 to 90°F (4.5°C to 32°C)

(increments: 0.5° or 5°)

Occ HT

Return air sensor network lost

occupied heating setpoint

Default: 72°F

If network communication is lost with the zone controllers,

the return air sensor will control the RTC to maintain this

setpoint.

40 to 90°F (4.5°C to 32°C)

(increments: 0.5° or 5°)

Unocc CL

Return air sensor network lost

unoccupied cooling setpoint

Default: 82°F

If network communication is lost with the zone controllers,

the return air sensor will control the RTC to maintain this

setpoint.

54 to 100°F (12°C to 37.5°C)

(increments: 0.5° or 5°)

Unocc HT

Return air sensor network lost

unoccupied heating setpoint

Default: 65°F

If network communication is lost with the zone controllers,

the return air sensor will control the RTC to maintain this

setpoint.

40 to 90°F (4.5°C to 32°C)
(increments: 0.5° or 5°)

Sp range

Static Pressure sensor range

Default: 0

Static pressure transducer range. Voltage input range is 0
to 5 VDC.

0 = 0 to 1.5 in WC
1 = 0 to 2 in WC
2 = 0 to 3 in WC
3 = 0 to 4 in WC

4 = 0 to 5 in WC