25 | VZ7656E1000W Installation Guide

Pressure

Static Pressure setpoint

Default:

0.8”WC

Bypass damper will maintain this supply static pressure
set point.

Please refer to the Viconics Zoning System Guide for

recommended settings.

0 to 2 in WC (0 Pa to 500 Pa)
(increments: 0.1” WC or 25 Pa)

SP Cntrl

Static Pressure Control Type

Default: BPD

Depending on the setting of this parameter, the 0-10VDC

pressure control output (labled BPD) will either have a

0VDC or 10VDC output when the fan is Off.

BPD (By-Pass Damper): 10VDC when fan Off

VFD (Variable Frequency Drive): 0VDC when fan Off

Chngstpt

changeover setpoint

Default value = 55 °F(13.0 °C)

In Cooling mode.

The outside air temperature value at which the cooling will

be switched over from mechanical ( compressor ) to free

cooling ( economizer )

14 to 70 °F ( -10.0 to 21.0 °C )

mix stpt

Mixed air setpoint

Default value = 55 °F ( 13.0

°C )

Free cooling mixed air setpoint when economizer mode is

enabled.

50 to 90 °F ( 10.0 to 32.0 °C )

Min Pos

Minimum Fresh Air

Damper/Economizer Position

Default value = 0%

Minimum fresh air damper position. Effective only in

Occupied mode (Fan is ON). This value is also used to

determine the fresh air damper position based on the

Min/Max CO2 and Min/Max Pos values set. See Fresh Air

Damper Position section for more details.

0% to 100%, 1 or 10 increments

Max Pos

Maximum Fresh Air

Damper/Economizer Position

Default value = 100%

Maximum fresh air damper position. Effective only in

Occupied mode (Fan is ON). This value is used to

determine the fresh air damper position based on the

Min/Max CO2 and Min/Max Pos values set. See Fresh Air

Damper Position section for more details.

0% to 100%, 1 or 10 increments