20 | VZ7656E1000W Installation Guide

Channel

Channel selection

Default value = 10

Range is: 10 to 26

This parameter (Channel) is used to link specific
controllers to specific Viconics wireless gateway(s)
(VWG / Jace-Driver) or to the main VZ76xx RTU
controller. For any system, be sure you set the SAME
channel value both at the network coordinator and on all
the VZ72xx controller(s).

Viconics recommends using only the following channels:
15, 25 & 26.

The default value of 10 is NOT a valid channel. The valid
range of available channels range from 11 to 26.

Lockout Keypad lockout levels

Default value = 0 No lock

0 = No lock
1 = Low level
2 = High level