29 | VZ7656E1000W Installation Guide

Economizer Mode and CO

2

Level Control

If the fresh air damper is to be used for both free cooling and CO

2

level control

(economizer mode and CO

2

level control, but without fresh air measurement station), only

the Min Pos, Max Pos, Min CO

2

and Max CO

2

parameters as well as the free cooling

sequence will be active.

-

The FA Range parameter should be set to 0 CFM.

-

Set AI1 parameter to CO

2

(0 VDC = 0ppm ; 10VDC = 2000ppm)

-

Min Pos, Max Pos, Min CO

2

and Max CO

2

parameters should be set

according to the required setting.


The highest value between free cooling demand output and interpolation output
for the fresh air setpoint will be the output to the fresh air damper.


Min Pos

Max Pos

Min CO

2

Max CO

2

Current
Fresh Air
Setpoint

Current CO

2

Level