23 | VZ7656E1000W Installation Guide

Cal OS
Outside air temperature
sensor calibration
Default value = 0.0 °F or °C

Offset that can be added/subtracted to actual displayed
outside air temperature
± 5.0 °F ( ± 2.5 °C )

H stage

Number of heating stages

installed at RTU.

Default value = 2 stages

Will revert the operation of 2 stage controllers to a single

stage when the second heating step is not needed.

1 or 2 stages

C stage

VZ7656R1000B models only

Number of cooling stages

installed at RTU.

Default value = 2 stages

Will revert the operation of 2 stage controllers to a single

stage when the second cooling step is not needed.

1 or 2 stages

H lock
Outside air temperature
heating lockout
Default value = 120 °F (49
°C)

Disables heating stage operation based on outdoor air
temperature.
Function will only be enabled if OS ( outside air
temperature sensor ) is connected.
From -15 °F up to 120 °F (-26 °C up to 49 °C)

C lock
Outside air temperature
mechanical cooling lockout.
Default value = -40 °F (40 °C)

Disables cooling stage operation based on outdoor air
temperature.
On economizer model, free cooling will not be disabled by
this function.
Function will only be enabled if OS (outside air
temperature sensor) is connected.
From -40 °F up to 95 °F ( -40 °C up to 35 °C )

2/4event
Number of events
configuration
Default value = 2 event

2 events, will set up scheduling for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
4 events, will set up scheduling for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
Event 3 is for Occupied setpoints
Event 4 is for Unoccupied setpoints

FA Range

FA range upper limit value

Default value = 0 CFM

Sets the upper limit of the CFM range. This parameter

should be set based on the rooftop unit size. If set to 0

CFM, the fresh air damper control will be based on the

Min/Max CO2 and Min/Max Pos values. See Damper

Position section for more details.

0 to 20 000 CFM (0 to 9438 L/s), 10 or 100 increments