User interface, User configuring instructions menu – Viconics VZ7656E Installation Guide User Manual
Page 11

11 | VZ7656E1000W Installation Guide
Current
Zone
Sequence
Return Air
Temperature
Discharge
Air
Temperature
Current Static
Pressure
Fresh Air
Level
Zone Seq
RA Temp
DA Temp
Pressure
FA Level
Off
xx.x °C or °F
xx.x °C or °F
x.x WC or Pa
xxxxxCFM
Zone Seq
Cool
Zone Seq
Heat
Effective
PI Heat
Demand
at RTU
Effective
PI Cool
Demand
at RTU
Effective
CO2 Level
at RTU
Highest PI
Heat
Demand
Zone
Address
Highest PI
Cool
Demand
Zone
Address
Highest
CO2 Level
Zone
Address
Heat Out
Cool Out
CO2 Lvl
Heat MAC
Cool MAC
CO2 MAC
xxx %
xxx %
xxxx ppm
xxx
xxx
xxx
DAS
Alarm
Indicates that the discharge air temperature is either too low or too high.
FA Alarm
Indicates that the Fresh Air Level is either too low or too high.
SetClock
Indicates that the clock needs to be reset. There has been a power failure
which has lasted longer than 6 hours.
High CO2
Indicates that the CO
2
Level value is higher than the Max CO
2
parameter
value.
Com Lost
The communication between devices has been lost (No Communication)
When any of the fan is ON, the FAN LED will illuminate
When heating is ON, the HEAT LED will illuminate
When cooling is ON, the COOL LED will illuminate
U
SER INTERFACE
User configuring instructions menu
The VZ7656 series of controllers feature an intuitive,
menu-driven, back-lit LCD display that walks users and
installers through the configuring steps, making the
configuring process extremely simple. This menu is
typically accessed by the user to set the parameters
such as the clock time set, the schedule time events
and the system mode.