beautypg.com

Viconics VT7200 (Echelon) Integration Manual User Manual

Page 21

background image

21


VT73xxX Integration – Graphic User Interface (GUI) objects


The following objects should be typically used in a GUI:

nvoSpaceTemp
occupied_heat (nciSetpts);
unoccupied_heat (nciSetpts);
occupied_cool (nciSetpts);
unoccupied_cool (nciSetpts);
nvoSpaceRH
RHsetpoint (nciRHmodel);
nvoOutdoorTemp
nvoDischAirTemp
nviOccManCmd
nvoEffectOccup
heat_output_primary (nvoUnitStatus)
cool_output (nvoUnitStatus)
ServiceAlarm (nvoSccStatus)
FilterAlarm (nvoSccStatus)
WindowOpened (nvoSccStatus)


Graphical User Interface (GUI) example of a Fan-Coil system