Note 1:
How to use nviHeatCool, nviAuxHeatEnable and SeqOpera (Sequence of Operation) variables:

Current
nviHeatCool

NviAuxHeat
Enable =
Enabled

NviAuxHeat
Enable =
Disabled

Current SeqOpera

If nviHeatCool
changed to:

New SeqOpera

2 Pipe Application

3 = HVAC_COOL

X

0 = Cooling Only

1= HVAC_HEAT

1 = Heating Only

3 = HVAC_COOL

X

2 = Cooling & Reheat

1= HVAC_HEAT

3 = Heating & Reheat

1 = HVAC_HEAT

X

1 = Heating Only

3= HVAC_COOL

1 = Cooling Only

1 = HVAC_HEAT

X

3 = Heating & Reheat

3= HVAC_COOL

2 = Cooling & Reheat

4 Pipe Application

3 = HVAC_COOL

X

0 = Cooling Only

0= HVAC_AUTO
1= HVAC_HEAT

4 = Cool/Heat 4 Pipes
1 = Heating Only

3 = HVAC_COOL

X

2 = Cooling & Reheat

0= HVAC_AUTO
1= HVAC_HEAT

5 = Cool/Heat 4P & Reheat
3 = Heating & Reheat

1 = HVAC_HEAT

X

1 = Heating Only

0= HVAC_AUTO
3= HVAC_COOL

4 = Cool/Heat 4 pipes
1 = Cooling Only

1 = HVAC_HEAT

X

3 = Heating & Reheat

0= HVAC_AUTO
3= HVAC_COOL

5 = Cool/Heat 4P & Reheat
2 = Cooling & Reheat

0 = HVAC_AUTO

X

4 = Cool/Heat 4 Pipes

1= HVAC_HEAT
3= HVAC_COOL

1 = Heating Only
0 = Cooling Only

0 = HVAC_AUTO

X

5 = Cool/Heat 4P &

Reheat

1= HVAC_HEAT
3= HVAC_COOL

3 = Heating & Reheat
2 = Cooling & Reheat