Viconics VT7200 (Echelon) Integration Manual User Manual
Page 14

14
Configuration Properties (nci’s) Description
Parameter Variable
Name Function
This configuration property defines the space temperature
setpoints for various heat, cool and occupancy modes.
Valid Range and Default values:
Sub
Name
Valid Range
Default value
01
occupied_cool
54 to 100°F
(12 to 37.5°C)
75°F (24.0°C)
02
standby_cool
54 to 100°F
(12 to 37.5°C)
78°F (25.5°C)
03
unoccupied_cool
54 to 100°F
(12 to 37.5°C)
80°F (26.5°C)
04
occupied_heat
40 to 90°F
(4.5 to 32°C)
72°F (22.0°C)
05
standby_heat
40 to 90°F
(4.5 to 32°C)
69°F (20.5°C)
Temperature
Setpoints
network input config
SNVT_temp_setpt
nciSetPts
06
unoccupied_heat
40 to 90°F
(4.5 to 32°C)
62°F (16.5°C)
This configuration property defines the space humidity parameters
and their settings.
Valid Range and Default values:
Sub
Name
Valid Range
Default value
01
bi1 config
0 = None
1 = Rem NSB
2 = Motion NO
3 = Motion NC
4 = Window
0 = None
02
bi2 config
0 = None
1 = Door Dry
2 = Override
3 = Filter
4 = Service
0 = None
03
ui3 config
0 = None
1 = COC/NH
2 = COC/NC
3 = COS
4 = SS
0 = None
04
room humidity display
0 = Not active
1 = Active
0 = Not active
05 dehumidification
setpoint
30 to 100% RH
50% RH
06 dehumidification
hysterisys
2 to 20% RH
5% RH
07 dehumidification
max
cooling
20 to 100% RH
100% RH
RH Model
Options
network input config
UNVT_cfg_2_fcu_zn
NciCfg2FcuZn
08
calib room humidity
sensor
-15 to +15% RH
0% RH