Parameter Variable
Name Function
This configuration property defines the thermostat’s common
configuration parameters and their settings.
Valid Range and Default values:
Thermostat
Common
Configuration
Parameters
network input config
UNVT_cfg_1_fcu_zn
nciCfg1FcuZn
Sub
Name
Valid Range
Default value
19
proportional band
3 to 10 F
3 F
20
aux contact config
0 = Aux Contact used
for reheat
1 = Aux NO with
occupancy
2 = Aux NC with
occupancy
3 = Aux NO with
occupancy & Fan
On
4 = Aux NC with
occupancy & Fan
On
5 = Remote control
nviAuxOut
0
21
reheat time base
0 = 15 minutes
1 = 10 seconds
0
22
fan mode
0 = Low
1 = Med
2 = High
3 = Auto
4 = On
Depending on
Fan Menu
Selected
23
auto fan
0 = Auto Speed
1 = Auto Speed and
Auto Demand
0 = Auto
Speed
24
pir stand-by timer
0.5 to 24.0 Hours
0.5 Hours
25
pir unoccupied timer
0.0 to 24.0 Hours
0.0 Hours