Parameter Variable

Name Function

This configuration property defines the thermostat’s common

configuration parameters and their settings.

Valid Range and Default values:

Thermostat
Common
Configuration
Parameters

network input config


UNVT_cfg_1_fcu_zn

nciCfg1FcuZn

Sub

Name

Valid Range

Default value

19

proportional band

3 to 10 F

3 F

20

aux contact config

0 = Aux Contact used
for reheat
1 = Aux NO with
occupancy
2 = Aux NC with
occupancy
3 = Aux NO with

occupancy & Fan
On

4 = Aux NC with

occupancy & Fan
On

5 = Remote control

nviAuxOut

0

21

reheat time base

0 = 15 minutes
1 = 10 seconds

0

22

fan mode

0 = Low
1 = Med
2 = High
3 = Auto
4 = On

Depending on
Fan Menu
Selected

23

auto fan

0 = Auto Speed
1 = Auto Speed and
Auto Demand

0 = Auto
Speed

24

pir stand-by timer

0.5 to 24.0 Hours

0.5 Hours

25

pir unoccupied timer

0.0 to 24.0 Hours

0.0 Hours