Viconics VTR7300 BACnet Integration Manual User Manual
Page 9
9
Object Name
Type and Instance Object Property
VTR7
3
0
0
A5
x
0
0
B
VTR7
3
0
5
A5
x
0
0
B
VTR7
3
5
0
A5
x
0
0
B
VTR7
3
5
5
A5
x
0
0
B
Keypad Lockout
MV 19
PV (R,W)
Control Output
GRP 20
PV (R)
PI Heating Demand
AV 21
PV (R)
PI Cooling Demand
AV 22
PV (R)
Dehumidification Status
BI 23
PV (R)
Controller Status
GRP 24
PV (R)
Fan Status
MV 28
PV (R)
BI 1 Status
BI 29
PV (R)
BI 2 Status
BI 30
PV (R)
Local Motion
BI 32
PV (R)
Effective Occupancy
MV 33
PV (R)
Controller Alarms
GRP 34
PV (R)
Window Alarm
BI 35
PV (R)
Filter Alarm
BI 36
PV (R)
Service Alarm
BI 37
PV (R)
Temperature Setpoints
GRP 38
PV (R)
Occupied Heat Setpoint
AV 39
PV (R,W)
Occupied Cool Setpoint
AV 40
PV (R,W)
Stand-by Heat Setpoint
AV 41
PV (R,W)
Stand-by Cool Setpoint
AV 42
PV (R,W)
Unoccupied Heat
Setpoint
AV 43
PV (R,W)
Unoccupied Cool
Setpoint
AV 44
PV (R,W)
General Options 1
GRP 45
PV (R)
BI 1 Configuration
MV 46
PV (R,W)
BI 2 Configuration
MV 47
PV (R,W)
Menu Scroll
BV 49
PV (R,W)
Auto Mode Enable
BV 50
PV (R,W)
Temperature Scale
BV 51
PV (R,W)
Pipe Number
MV 52
PV (R,W)
General Options 2
GRP 55
PV (R)
Password Value
AV 56
PV (R)
Fan Mode Sequence
MV 57
PV (R,W)
Heating Setpoint Limit
AV 58
PV (R,W)