List of Property Enumeration Sets for MV Objects

Object Name

Object ID

BACnet Index

Text

Default value

Sequence of
Operation

MV 15

1

Cooling Only

Heating Only

2

Heating Only

3

Cooling & Reheat

4

Heating & Reheat

5

Cool/Heat4P

6

Cool/Heat4P&Reht

System Mode
Note 1

MV 16

1

Off

Note 2

2

Auto

3

Cool

4

Heat

Fan Mode
Note 3

MV 17

1, 2, 3 or 4

Note 4

Note 5

Occupancy
Command

MV 18

1

Local Occupancy

Depends on network
command

2

Occupied

3

Unoccupied

Keypad Lockout

MV 19

1

Level 0

Level 0

2

Level 1

3

Level 2

4

Level 3

5

Level 4

6

Level 5


Note 1
Enumeration sets for MV16 depends on Sequence of Operation (MV15) value upon device
discovery. If required enumeration is not present, set MV15 to desired value and rediscover MV16 object.
Available enumeration will now reflect required configuration.

Note 2 Default value of MV16 depends on MV15 value upon device discovery

MV15 Index

Function

Default Value is
BV50 Enabled

Default Value is
BV50 Disabled

1

Cooling Only

Cool

Cool

2

Cooling with Reheat

Auto

Heat

3

Heating Only

Heat

Heat

4

Heating with Reheat

Heat

Heat

5

Cooling/Heating 4 Pipes

Auto

Heat

6

Cooling/Heating 4 Pipes with Reheat

Auto

Heat


Note 3 Enumeration sets for MV17 depends on Fan Mode Sequence (MV58) value upon device discovery.
If required enumeration is not present, set MV58 to desired value and rediscover MV17 object. Available
enumeration will now reflect required configuration.

Note 4 & 5 Available state text and default value depends on Fan Mode Sequence (MV58) value upon
device discovery.

MV17 Index Function MV58 State Text Index

Default Value

1

1 Low - 2 Med - 3 High

High

2

1 Low - 2 High

High

3

1 Low - 2 Med - 3 High - 4 Auto

High

4

1 Low - 2 High - 3 Auto

High

5

1 Auto -2 On

Auto