Viconics VTR7300 BACnet Integration Manual User Manual
Page 14
14
List of Property Enumeration Sets for MV Objects
Object Name
Object ID
BACnet Index
Text
Default value
Sequence of
Operation
MV 15
1
Cooling Only
Heating Only
2
Heating Only
3
Cooling & Reheat
4
Heating & Reheat
5
Cool/Heat4P
6
Cool/Heat4P&Reht
System Mode
Note 1
MV 16
1
Off
Note 2
2
Auto
3
Cool
4
Heat
Fan Mode
Note 3
MV 17
1, 2, 3 or 4
Note 4
Note 5
Occupancy
Command
MV 18
1
Local Occupancy
Depends on network
command
2
Occupied
3
Unoccupied
Keypad Lockout
MV 19
1
Level 0
Level 0
2
Level 1
3
Level 2
4
Level 3
5
Level 4
6
Level 5
Note 1 Enumeration sets for MV16 depends on Sequence of Operation (MV15) value upon device
discovery. If required enumeration is not present, set MV15 to desired value and rediscover MV16 object.
Available enumeration will now reflect required configuration.
Note 2 Default value of MV16 depends on MV15 value upon device discovery
MV15 Index
Function
Default Value is
BV50 Enabled
Default Value is
BV50 Disabled
1
Cooling Only
Cool
Cool
2
Cooling with Reheat
Auto
Heat
3
Heating Only
Heat
Heat
4
Heating with Reheat
Heat
Heat
5
Cooling/Heating 4 Pipes
Auto
Heat
6
Cooling/Heating 4 Pipes with Reheat
Auto
Heat
Note 3 Enumeration sets for MV17 depends on Fan Mode Sequence (MV58) value upon device discovery.
If required enumeration is not present, set MV58 to desired value and rediscover MV17 object. Available
enumeration will now reflect required configuration.
Note 4 & 5 Available state text and default value depends on Fan Mode Sequence (MV58) value upon
device discovery.
MV17 Index Function MV58 State Text Index
Default Value
1
1 Low - 2 Med - 3 High
High
2
1 Low - 2 High
High
3
1 Low - 2 Med - 3 High - 4 Auto
High
4
1 Low - 2 High - 3 Auto
High
5
1 Auto -2 On
Auto