Viconics VTR7300 BACnet Integration Manual User Manual
Page 15
15
Object Name
Object ID
BACnet Index
Text
Default value
Output 2
Note 6
MV 26
Note 7
Note 7
Note 7
Output 1
Note 8
MV 27
Note 9
Note 9
Note 9
Fan Status
MV 28
1
Off
Off
2
Low
3
Med
4
High
Effective
Occupancy
MV 33
1
Occupied
Depends on local
occupancy
2
Unoccupied
3
Temporary Occupied
4
Stand-by
Note 6 Enumeration sets for MV26 depends on Control Type (BV75) value and Pipe Number (MV52) value
upon device discovery. If required enumeration is not present, set BV75 and MV52 to desired value and
rediscover MV26 object. Available enumeration will now reflect required configuration.
Note 7 Available object name, state text and default value depends on Control Type (BV75) value and Pipe
Number (MV52) upon device discovery.
BV75 Value
MV52 Index
MV26 Object
Name
Function MV26 State Text Index
Default Value
On/Off
1 (2 pipe)
Unused Output
N/A
N/A
2 (4 pipe)
Output 2
1 Closed
– 2 Open
Closed
Floating
1 (2 pipe)
Unused Output
N/A
N/A
2 (4 pipe)
Output 2
1 Stopped - 2 Opening - 3 Closing Stopped
Note 8 Enumeration sets for MV27 depends on Control Type (BV75) value and Pipe Number (MV52) value
upon device discovery. If required enumeration is not present, set BV75 and MV52 to desired value and
rediscover MV27 object. Available enumeration will now reflect required configuration.
Note 9 Available object name, state text and default value depends on Control Type (BV75) value and Pipe
Number (MV52) upon device discovery.
BV75 Value
MV52 Index
MV27 Object
Name
Function MV26 State Text Index
Default Value
On/Off
1 (2 pipe)
Heat/Cool Valve
Status
1 Closed
– 2 Open
Closed
2 (4 pipe)
Output 1
1 Closed
– 2 Open
Closed
Floating
1 (2 pipe)
Heat/Cool Valve
Status
1 Stopped - 2 Opening - 3 Closing Stopped
2 (4 pipe)
Output 1
1 Stopped - 2 Opening - 3 Closing Stopped