RH Display
BV 70
Disabled
Enabled
Disabled
Control Type
BV 75
On/Off
Floating
On/Off
Direct/ Reverse Acting
BV 78
Direct Acting
Reverse Acting
Direst Acting
Heat NO NC
BV 86
Normally
Opened
Normally Closed
Normally
Closed
Cool NO NC
BV 87
Normally
Opened
Normally Closed
Normally
Closed
RUI 1 Status
BI 91
Deactivated
Activated
Deactivated
RBI 2 Status
BI 92
Deactivated
Activated
Deactivated
Cooling Valve Status
BI 93
Off
On
Off
Heating Valve Status
BI 94
Off
On
Off
(*) This object will be linked to the value of the ‘UI 3 Configuration’ object. When the ‘UI
3 Configuration’ object value is 0, 3 or 4, the value will be set to ‘Deactivated’