Troubleshooting Section

Error / Trouble
Condition

Possible Cause

Solution

Thermostat does not
come online

Two or more controllers have the same
MAC address.

Modify each duplicate address to a
unique number.

The MS/TP network has too many
devices.

Do not exceed the maximum number of
devices and maximum length allowed
by the EIA-485 specifications.

Too many devices were installed
without any repeaters.

Repeaters need to be installed as
specified in this document.

The MS/TP cable runs are broken

Locate the break and correct wiring

MS/TP connections at the module are
reversed

Respect polarity of the wires on a
MS/TP network.

The thermostat does not have power

Apply power to the thermostat