Viconics VTR7300 BACnet Integration Manual User Manual
Page 31
31
Troubleshooting Section
Error / Trouble
Condition
Possible Cause
Solution
Thermostat does not
come online
Two or more controllers have the same
MAC address.
Modify each duplicate address to a
unique number.
The MS/TP network has too many
devices.
Do not exceed the maximum number of
devices and maximum length allowed
by the EIA-485 specifications.
Too many devices were installed
without any repeaters.
Repeaters need to be installed as
specified in this document.
The MS/TP cable runs are broken
Locate the break and correct wiring
MS/TP connections at the module are
reversed
Respect polarity of the wires on a
MS/TP network.
The thermostat does not have power
Apply power to the thermostat