Viconics VTR7300 BACnet Integration Manual User Manual

Page 12

background image

12

List of Property Value Range Restrictions

Object name

Object Type

and instance

Minimum range

value

Maximum

range value

Default value

Room Temperature

AV 7

-39.9°F (-40°C)

121.9°F (50°C)

N/A

Outdoor Temperature

AV 9

-39°F (-40°C)

121.9°F (50°C)

N/A

Room Humidity

AV 10

5%

90%

N/A

A02 ECM Value

AV 10

0 %

100%

N/A

Supply Temperature

AI 12

-39.9°F (-40°C)

121.9°F (50°C)

N/A

PI Heating demand

AV 21

0%

100%

0%

PI Cooling demand

AV 22

0%

100%

0%

Occupied Heat Setpoint

AV 39

40°F (4.5°C)

90°F (32°C)

72°F (22°C)

Occupied Cool Setpoint

AV 40

54°F (12°C)

100°F (37.5°C)

74°F (24°C)

Stand-by Heat Setpoint

AV 41

40°F (4.5°C)

90°F (32°C)

72°F (22°C)

Stand-by Cool Setpoint

AV 42

54°F (12°C)

100°F (37.5°C)

74°F (24°C)

Unoccupied Heat Setpoint

AV 43

40°F (4.5°C)

90°F (32°C)

62°F (16.5°C)

Unoccupied Cool Setpoint

AV 44

54°F (12°C)

100°F (37.5°C)

80°F (26.5°C)

RH Setpoint

AV 45

30%

100%

50%

Dehumidification Hysterisys

AV 46

2%

20%

5%

Dehumidification MAX
cooling

AV 47

20%

100%

100%

Password Value

AV 56

0

1000

N/A

Heating Setpoint Limit

AV 58

40°F (4.5°C)

90°F (32°C)

90°F (32°C)

Cooling Setpoint Limit

AV 59

54°F (12°C)

100°F (37.5°C)

54°F (12°C)

Deadband

AV 63

2°F (1°C)

5°F (2.5°C)

2°F (1°C)

Stand-by Time

AV 67

0.5 Hours

24.0 Hours

0.5 Hours

Unoccupied Time

AV 68

0.0 Hours

24.0 Hours

0.0 Hours

RH Setpoint

AV 71

30%

95%

50%

Dehumidification Hysterisys

AV 72

2%

20%

5%

Dehumidification MAX
Cooling

AV 73

20%

100%

100 %

Heat Demand Limit

AV 88

0%

100%

N/A

Cool Demand Limit

AV 89

0%

100%

N/A


List of Property Enumeration Sets for BV Objects and BI Objects

Object Name

Object

Type and

instance

Inactive_Text

Active_Text

Default value

Room Temp Override

BV 8

Normal

Override

Normal

Room Humidity Override

BV 11

Normal

Override

Normal

Dehumidification Lockout

BV 13

Disabled

Enabled

Enabled

AUX Command

BV 14

Off

On

Off

Dehumidification Status

BI 23

Off

On

Off

Aux Status

BI 25

Off

On

Off

BI 1 Status

BI 29

Deactivated

Activated

Deactivated

BI 2 Status

BI 30

Deactivated

Activated

Deactivated

UI 3 Status(*)

BI 31

Deactivated

Activated

Deactivated

Local Motion

BI 32

No Motion

Motion

No Motion

Window Alarm

BI 35

Off

On

Off

Filter Alarm

BI 36

Off

On

Off

Service Alarm

BI 37

Off

On

Off

Menu Scroll

BV 49

No Scroll

Scroll Active

Scroll Active

Auto Mode Enable

BV 50

Disabled

Enabled

Enabled

Temperature Scale

BV 51

°C

°F

°F

Setpoint Type

BV 60

Permanent

Temporary

Permanent

Setpoint Function

BV 61

Dual Setpoints

Attached

Setpoints

Dual Setpoints

Reheat Time Base

BV 64

15 minutes

10 seconds

15 minutes

Auto Fan

BV 66

Auto Speed

Auto Speed /

Auto Demand

Auto Speed