Viconics VTR7300 BACnet Integration Manual User Manual
Page 12
12
List of Property Value Range Restrictions
Object name
Object Type
and instance
Minimum range
value
Maximum
range value
Default value
Room Temperature
AV 7
-39.9°F (-40°C)
121.9°F (50°C)
N/A
Outdoor Temperature
AV 9
-39°F (-40°C)
121.9°F (50°C)
N/A
Room Humidity
AV 10
5%
90%
N/A
A02 ECM Value
AV 10
0 %
100%
N/A
Supply Temperature
AI 12
-39.9°F (-40°C)
121.9°F (50°C)
N/A
PI Heating demand
AV 21
0%
100%
0%
PI Cooling demand
AV 22
0%
100%
0%
Occupied Heat Setpoint
AV 39
40°F (4.5°C)
90°F (32°C)
72°F (22°C)
Occupied Cool Setpoint
AV 40
54°F (12°C)
100°F (37.5°C)
74°F (24°C)
Stand-by Heat Setpoint
AV 41
40°F (4.5°C)
90°F (32°C)
72°F (22°C)
Stand-by Cool Setpoint
AV 42
54°F (12°C)
100°F (37.5°C)
74°F (24°C)
Unoccupied Heat Setpoint
AV 43
40°F (4.5°C)
90°F (32°C)
62°F (16.5°C)
Unoccupied Cool Setpoint
AV 44
54°F (12°C)
100°F (37.5°C)
80°F (26.5°C)
RH Setpoint
AV 45
30%
100%
50%
Dehumidification Hysterisys
AV 46
2%
20%
5%
Dehumidification MAX
cooling
AV 47
20%
100%
100%
Password Value
AV 56
0
1000
N/A
Heating Setpoint Limit
AV 58
40°F (4.5°C)
90°F (32°C)
90°F (32°C)
Cooling Setpoint Limit
AV 59
54°F (12°C)
100°F (37.5°C)
54°F (12°C)
Deadband
AV 63
2°F (1°C)
5°F (2.5°C)
2°F (1°C)
Stand-by Time
AV 67
0.5 Hours
24.0 Hours
0.5 Hours
Unoccupied Time
AV 68
0.0 Hours
24.0 Hours
0.0 Hours
RH Setpoint
AV 71
30%
95%
50%
Dehumidification Hysterisys
AV 72
2%
20%
5%
Dehumidification MAX
Cooling
AV 73
20%
100%
100 %
Heat Demand Limit
AV 88
0%
100%
N/A
Cool Demand Limit
AV 89
0%
100%
N/A
List of Property Enumeration Sets for BV Objects and BI Objects
Object Name
Object
Type and
instance
Inactive_Text
Active_Text
Default value
Room Temp Override
BV 8
Normal
Override
Normal
Room Humidity Override
BV 11
Normal
Override
Normal
Dehumidification Lockout
BV 13
Disabled
Enabled
Enabled
AUX Command
BV 14
Off
On
Off
Dehumidification Status
BI 23
Off
On
Off
Aux Status
BI 25
Off
On
Off
BI 1 Status
BI 29
Deactivated
Activated
Deactivated
BI 2 Status
BI 30
Deactivated
Activated
Deactivated
UI 3 Status(*)
BI 31
Deactivated
Activated
Deactivated
Local Motion
BI 32
No Motion
Motion
No Motion
Window Alarm
BI 35
Off
On
Off
Filter Alarm
BI 36
Off
On
Off
Service Alarm
BI 37
Off
On
Off
Menu Scroll
BV 49
No Scroll
Scroll Active
Scroll Active
Auto Mode Enable
BV 50
Disabled
Enabled
Enabled
Temperature Scale
BV 51
°C
°F
°F
Setpoint Type
BV 60
Permanent
Temporary
Permanent
Setpoint Function
BV 61
Dual Setpoints
Attached
Setpoints
Dual Setpoints
Reheat Time Base
BV 64
15 minutes
10 seconds
15 minutes
Auto Fan
BV 66
Auto Speed
Auto Speed /
Auto Demand
Auto Speed