Viconics VTR7300 BACnet Integration Manual User Manual
Page 5
5
Objects Table
Object Name
Type and
Instance
Object Property
Thermostat Parameter
VT7200X5x00B
VT73xxX5X00B
Device
Object_Identifier
Property 75 (R,W)
Unique ID number of a device on a network
Object_Name
Property 77 (R,W)
Unique name of a Device on a network
Model Name
Property 70 (R)
Thermostat Model number
Firmware Revision
Property 44 (R)
Current BACnet firmware revision used by the
thermostat
Protocol Version
Property 98 (R)
Current BACnet firmware protocol version
Default is Version 1
Protocol Revision
Property 139 (R)
Current BACnet firmware protocol revision
Default is Version 2
Max ADPU Length
Property 62 (R)
Maximum ADPU Length accepted
Default is 244
ADPU Timeout
Property 10 (R)
ADPU timeout value
Default is60 000 ms
Application-
Software-Version
Property 12 (R)
Thermostat base application software version
Default is based on current released version
Max_Master (R,W)
Maximum master devices allowed being part of
the network. 0 to 127, default is 127
MS/TP_Address
Property 1001 (R,W)
BACnet MS-TP MAC Address. Proprietary
attribute. Default is as assigned by configuration
MS/TP_Baud_Rate
Property 1002 (R,W)
BACnet MS-TP Baud-Rate. Proprietary attribute.
Range is: 1 = 9.6 KBps, 2 = 19.2 KBps, 3 = 38.4
KBps, 4 = 76.8 KBps and 5 = Auto Baud Rate.
Index 5 is Write only. Reading attribute will state
current Baud rate used. Writing index 1 to 4 will fix
the Baud rate to the desired value.