Viconics VTR7300 BACnet Integration Manual User Manual
Page 18
18
Object Name
Object ID
BACnet Index
Text
Default value
Floating Motor
Timing
MV 76
1
0.5 minute
1.5 minutes
2
1 minute
3
1.5 minutes
4
2 minutes
5
2.5 minutes
6
3 minutes
7
3.5 minutes
8
4 minutes
9
4.5 minutes
10
5 minutes
11
5.5 minutes
12
6 minutes
13
6.5 minutes
14
7 minutes
15
7.5 minutes
16
8 minutes
17
8.5 minutes
18
9 minutes
On-Off Control
CPH
MV 77
1
3 CPH
4 CPH
2
4 CPH
3
5 CPH
4
6 CPH
5
7 CPH
6
8 CPH
RUI 1 Configuration
MV 82
0
None
None
1
Filter
2
Service
3
COC/NH
4
COC/NC
5
COS
RBI 2 Configuration
MV 83
0
None
None
1
Filter
2
Service
This manual is related to the following products: