Parameter Variable

Name

Function

This configuration property defines model number and software

version of the thermostat

Valid Range and Default values:

Sub

Name

Valid Range

Default value

01

Thermostat Model 11 = VT7600A

12 = VT7600H
10 = VT7600B
09 = VT7605B
02 = VT7652A
06 = VT7652B
01 = VT7656B
04 = VT7652H

Depend on model
being used

Thermostat’s
model number

network input config
UNVT_model_info_2
nciSccModel

02

Software Version

Unsigned short

Thermostat dependent

Maximum
Send Time

network input config
SNVT_time_sec
nciSendHrtBt

This configuration property defines the maximum period of time that

expires before the specified network variable outputs will automatically
be updated

Valid Range: 0 sec. To 6553.4 sec.. Setting nciSendHrtBt to 0

disables the Send Heartbeat mechanism.

Default Null Value : 0.0 sec (no automatic update)

Minimum
Send Time

network input config
SNVT_time_sec
nciMinOutTm

This configuration property defines the minimum period of time

between automatic network variable outputs transmissions.

Valid Range: 0 sec. to 6553.4 sec.. Setting nciRcvHrtBt to 0 disables

the Minimum Send Time mechanism.

Default Null Value : 0.0 sec (no minimum send time)

Minimum
Receive
Time

network input config
SNVT_time_sec
nciRcvHrtBt

This configuration property is used to control the maximum time that

elapses after the last update to a specified network variable input
before the Space Comfort Controller starts to use its default values.

Valid Range: 0 sec. to 6553.4 sec.. Setting nciRcvHrtBt to 0 disables

the Receive Heartbeat mechanism.

Default Null Value : 0.0 sec (no failure detected)

Hardware or
Software
revisions

network input config
SCPT_maj_ver
nciMajVer

This configuration property defines the major module software

revisions.

Valid Range: 0 to 255

Hardware or
Software
revisions

network input config
SCPT_min_ver
nciMinVer

This configuration property defines the minor module software

revisions.

Valid Range: 0 to 255

Location
Label

network input config
SNVT_str_asc
nciLocation

This configuration property can optionally be used to provide more

descriptive physical location information than can be provided by the
Neuron Chip’s 6 byte location string. The location relates to the object
and not to the node.

Valid Range: Any NULL terminated ASCII string of 31 bytes total length