Parameter Variable

Name

Function

Setpoint network

output

SNVT_temp_p
nvoEffectSetpt

This output network variable is used to monitor the effective

temperature setpoint which may depend on nciSetpoints,
nvoEffectOccup, nviSetpoint and any local setpoint adjustment.
For example, if the occupancy state is unoccupied and the
heat/cool state is heat, the effective setpoint would be equal to
the unoccupied heating setpoint defined in nciSetpoints.

Valid Range: -40 to 100°F (-40 to 37.5°C)

Local setpoint
output

network output
SNVT_temp_p
nvoSetPoint

This output network variable is used to monitor the space

temperature setpoint

Valid Range : 40°F to 100°F (4.5°C to 37.5°C)

The present value is derived by the following

OccHeat Setpoint + ((OccCool Setpoint – OccHeat Setpoint ) / 2)




Configuration properties (nci’s) Description

Parameter Variable

Name Function

This configuration property defines the schedule for every day of

the week (from Monday to Sunday or from day 0 to day 6). This
nci is linked with the nvoEffectOccup variable.

2 or 4 events can entered depending on the nb_of_events

variable.

Starting and ending time are entered in minutes, e.i. 11:59 pm is

equal to 1439 minutes (23 hours * 60 min + 59 min)

Valid Range : 0 to 1439 minutes
Default values:

Sub Name

Default

Value

1 occupied_event_1

0

2 unoccupied_event_2 1439
3 occupied_event_3

0

Schedule

network input config
UNVT_day_sched
nciDay_Sched[x]
x
= 0 to 6

4 unoccupied_event_4 1439

This configuration property defines the space temperature

setpoints for various heat, cool and occupancy modes.

The stand-by setpoints can be modified but are not used by the

controller, as it does not support Stand-By occupancy mode.

Valid Range and Default values:

Sub

Name

Valid Range

Default value

01

occupied_cool

54 to 100°F
(12 to 37.5°C)

73.5°F (23°C)

02 standby_cool Not Used

Not Used

03

unoccupied_cool

54 to 100°F
(12 to 37.5°C)

82.5°F (28°C)

04

occupied_heat

40 to 90°F
(4.5 to 32°C)

70°F (21°C)

05 standby_heat Not Used

Not Used

Temperature
Setpoints

network input config
SNVT_temp_setpt
nciSetPts

06

unoccupied_heat

40 to 90°F
(4.5 to 32°C)

61°F (16°C)