beautypg.com

Viconics VT7600 Echelon Integration Manual User Manual

Page 12

background image

12

Parameter Variable

Name Function

This configuration property defines the thermostat’s common

configuration parameters and their settings.

Valid Range and Default values:

Name

Valid Range

Default value

password

0 to 1000

0

unoccupied timer

0.5 to 24.0 hours

0.5

anticycle

0, 1, 2, 3, 4, or 5 minutes

2 minutes

power-up delay

10 to 120 sec.

10 sec.

temporary occ time

0, 1, 2, 3 to 12 hours

3 hours

heating stages cph

3, 4, 5, 6, 7 or 8 CPH

4 CPH

cooling stages cph

3 or 4 CPH

4 CPH

heat maximum
setpoint

40 to 90°F (4.5 to 32°C)

90°F

cool minimum
setpoint

54 to 100°F
(12 to 37.5°C)

54°F

oa temp heat lockout -15 to 120°F (-26 to 49°C)

120°F

oa temp cool
lockout

-40 to 95°F (-40 to 35°C)

-40°F

calib room sensor

±5°F (±2.5°C)

0°F

calib outdoor air
sensor

±5°F (±2.5°C)

0°F

deadband

2 to 4°F with 1°F increments
(1 to 2°C)

2°F

fan mode

0 = On
1 = Auto
2 = Smart

0 = On

fan control

0 = Off
1 = On

1 = On

fan delay

0 = Off
1 = On

0 = Off

keypad lockout

0 = No_Lockout
1 = Level_1
2 = Level_2

No_Lockout

proportional band

2 to 8 F

2 F

temperature units

0 = °C
1 = °F

°F

frost protection

0 = Off
1 = On

0 = Off

Thermostat’s
common
configuration
parameters
network input
config

UNVT_cfg_1_rtu_hp

nciCfg1RtuHpt

temperature scale

0 = °C
1 = °F

°F