Parameter Variable
Name Function
This configuration property defines the thermostat’s common
configuration parameters and their settings.
Valid Range and Default values:
Name
Valid Range
Default value
password
0 to 1000
0
unoccupied timer
0.5 to 24.0 hours
0.5
anticycle
0, 1, 2, 3, 4, or 5 minutes
2 minutes
power-up delay
10 to 120 sec.
10 sec.
temporary occ time
0, 1, 2, 3 to 12 hours
3 hours
heating stages cph
3, 4, 5, 6, 7 or 8 CPH
4 CPH
cooling stages cph
3 or 4 CPH
4 CPH
heat maximum
setpoint
40 to 90°F (4.5 to 32°C)
90°F
cool minimum
setpoint
54 to 100°F
(12 to 37.5°C)
54°F
oa temp heat lockout -15 to 120°F (-26 to 49°C)
120°F
oa temp cool
lockout
-40 to 95°F (-40 to 35°C)
-40°F
calib room sensor
±5°F (±2.5°C)
0°F
calib outdoor air
sensor
±5°F (±2.5°C)
0°F
deadband
2 to 4°F with 1°F increments
(1 to 2°C)
2°F
fan mode
0 = On
1 = Auto
2 = Smart
0 = On
fan control
0 = Off
1 = On
1 = On
fan delay
0 = Off
1 = On
0 = Off
keypad lockout
0 = No_Lockout
1 = Level_1
2 = Level_2
No_Lockout
proportional band
2 to 8 F
2 F
temperature units
0 = °C
1 = °F
°F
frost protection
0 = Off
1 = On
0 = Off
Thermostat’s
common
configuration
parameters
network input
config
UNVT_cfg_1_rtu_hp
nciCfg1RtuHpt
temperature scale
0 = °C
1 = °F
°F