Parameter Variable

Name Function

Name

Valid Range

Default value

di1 config

0 = None
1 = RemNSB
2 = RemOVR
3 = Filter
4 = Service

0 = None

di2 config

0 = None
1 = RemNSB
2 = RemOVR
3 = Filter
4 = Service

0 = None

aux contact config

0 = NORMALLY_OPEN
1 = NORMALLY_CLOSE

0

number of events

2 or 4

2

progressive recovery

0 = Off
1 = Active

0 = Off

a.hp rev valve config

1 = Normally Heat
2 = Normally Cool

2

a.number of heating
stages

1 = 1 Stage
2 = 2 Stages

2

number of cool or hp
stages

1 = 1 Stage
2 = 2 Stages

2

econo min position

0 to 100%

0%

b.hp high balance
point

34 to 90°F (1 to 32°C)

90°F

b.econo changeover
setpoint

14 to 70°F (-10 to 21°C)

55°F

c.hp low balance
point

-40 to 30°F(-40 to –1°C)

-12°F

c.econo mixed air
setpoint

50 to 90°F (10 to 32°C)

50°F

d.hp comfort or
economy mode

0 = Comfort
1 = Economy

0 = Comfort

d.econo mechanical
cool enable

0 = Off
1 = On

0 = Off

Thermostat’s
common
configuration
parameters
network input
config

UNVT_cfg_2_rtu_hp

nciCfg2RtuHpt

hp compressor
auxheat interlock

0 = Off
1 = On

0 = Off

This configuration property helps the user identify the type of equipment

being monitored.

Valid Range:

Value Identifier

Name

HVAC Unit-
Type
Identifier

network input
config
SNVT_hvac_type
nciHvacType

0
1
2
3
4
5
6
7
8
9

HVT_GENERIC –

Not Used

HVT_FAN_COIL
HVT_VAV –

Not Used

HVT_HEAT_PUMP
HVT_ROOFTOP
HVT_UNIT_VENT –

Not Used

HVT_CHIL_CEIL –

Not Used

HVT_RADIATOR –

Not Used

HVT_AHU –

Not Used

HVT_SLF_CONT –

Not Used

Generic
Fan Coil
Variable Air Volume Terminal
Heat Pump
Rooftop Unit
Unit Ventilator
Chilled Ceiling
Radiator
Air Handling Unit
Self-Contained Unit