10.

Twin.City.Fan.Engineering.Supplement.2-06

Drive Maintenance

V-belt.drives.need.periodic.inspection,.re-tensioning,.and.

occasional.belt.replacement..Follow.Table.5.on.page.11.

for.drive.inspections.and.maintenance..Proper.belt.ten-

sion.can.be.found.on.the.included.datasheet.specific.to.

each. fan.. A. log. should. be. kept. with. belt. tension. and.

replacement.information.

Bearing Maintenance

Proper.lubrication.of.the.fan.drive.bearings.helps.assure.

maximum.bearing.life..All.fans.are.equipped.with.decals.

indicating. re-lubrication. intervals. for. normal. operating.

conditions.. Bearings. should. be. inspected. after. the. first.

24.hours.of.operation.and.then.inspected.each.time.they.

are. lubricated.. Lubrication. schedules. for. the. included.

type.of.bearings.are.attached.to.the.fan..Note.that.all.

speeds. shown. do. not. apply. to. all. shaft. sizes. in. that.

group..Consult.the.factory.if.in.doubt.of.maximum.speed.

for. a. particular. bearing.. Note. that. every. installation. is.

different. and. the. frequency. of. re-lubrication. should. be.

adjusted.accordingly.

. On. high. moisture. applications. the. lubrication. fre-

quency.may.need.to.be.doubled.or.tripled.to.adequately.

protect.the.bearings..Double.the.relubrication.frequency.

on.fans.with.vertical.shafts.

. Observation.of.the.conditions.of.the.grease.expelled.

from.the.bearings.at.the.time.of.relubrication.is.the.best.

guide.as.to.whether.regreasing.intervals.and.amount.of.

grease.added.should.be.altered.

. Greases. are. made. with. different. bases.. There. are.

synthetic.base.greases,.lithium.base,.sodium.base,.etc..

Avoid.mixing.greases.with.different.bases..They.could.be.

incompatible. and. result. in. rapid. deterioration. or. break-

down.of.the.grease..The.lubrication.sticker.identifies.a.

list. of. acceptable. lubricants.. All. fan. shaft. bearings. are.

filled.with.a.lithium-based.grease.before.leaving.the.fac-

tory.unless.otherwise.specified..When.the.fans.are.start-

ed,.the.bearings.may.discharge.excess.grease.through.

the.seals.for.a.short.period.of.time..Do.not.replace.the.

initial. discharge. because. leakage. will. cease. when. the.

excess.grease.has.worked.out..Sometimes.the.bearings.

have. a. tendency. to. run. hotter. during. this. period.. This.

is.no.reason.for.alarm.unless.it.lasts.over.48.hours.or.

gets.very.hot.(over.200°F,.93°C).

. If. bearings. are. exhibiting. excessive. vibration. at. any.

time.or.are.running.hotter.than.200°F,.93°C,.the.bear-

ings. should. be. inspected. for. proper. lubrication,. align-

ment,. tightness. of. set. screws,. cap. bolts,. and. collars,.

and.inspected.for.signs.of.contamination.in.the.lubricant..

The.bearings.or.damaged.bearing.components.shall.be.

replaced.if.found.faulty.or.showing.signs.of.wear..When.

relubricating,.use.a.sufficient.amount.of.grease.to.purge.

the.seals..Rotate.bearings.by.hand.during.relubrication.

Wheel and Shaft Maintenance

Inspect.the.shaft.and.wheel.for.dirt.buildup,.corrosion,.

and.signs.of.excess.stress.or.fatigue.after.one.month.

of.service..Future.inspection.interval.shall.be.based.on.

findings.in.this.initial.inspection..Clean.the.components..

If. any. signs. of. damage,. stress,. or. fatigue. are. present.

(deformation,. cracks,. excessively. worn. surfaces). the.

part.shall.be.replaced..Any.material.buildup.on.rotating.

parts.or.parts.that.could.contact.rotating.parts.shall.be.

cleaned..If.the.wheel.is.removed.for.any.reason,.make.

sure. that. it. is. securely. attached. to. the. shaft. before.

restarting. the. fan.. The. wheel. and. shaft. shall. also. be.

inspected.any.time.excessive.vibration.is.observed.(filter.

in.readings.should.be.7.2.mm/s.RMS.or.less)..Reference.

ISO. 14694:2003,. “Industrial. Fans. –. Specifications. for.

Balance. Quality. and. Vibration. Levels”. for. more. details.

on.acceptable.fan.vibration.levels.

Structural Maintenance

All. structural. components. or. devices. used. to. support.

or.attach.the.fan.to.a.structure.should.be.checked.at.

regular. intervals.. Vibration. isolators,. bolts,. foundations,.

etc.,. are. all. subject. to. failure. from. corrosion,. erosion,.

and.other.causes..Improper.mounting.can.lead.to.poor.

operation.characteristics.or.fan.fatigue.and.failure..Check.

metallic. components. for. corrosion,. cracks,. or. other.

signs.of.stress..Replace.any.components.showing.any.

of. these. signs.. Concrete. should. be. checked. to. insure.

the.structural.integrity.of.the.foundation.and.repaired.or.

replaced.if.any.signs.of.damage.are.found.

. Where. the. fan. is. used. to. handle. toxic. gasses. or.

vapors,. the. housing,. and. welds. shall. be. inspected. for.

signs. of. corrosion. or. cracking. at. regular. intervals. to.

assure. no. toxic. gasses. can. escape.. The. condition. of.

the. coating. shall. be. inspected. as. well. to. verify. that.

bare.parts.of.the.fan.are.not.exposed..All.gaskets.and.

ducting.shall.be.inspected.for.signs.of.erosion.as.well..

An.initial.inspection.after.one.month.of.service.shall.be.

used.to.determine.an.appropriate.inspection.interval.

Fan Operation

Proper Use and Application

It.is.critical.that.fans.are.operated.only.as.their.design.

intended..Standard.construction.is.designed.for.standard.

applications.as.defined.below:

•. Clean.air.–.no.solids,.particles,.or.corrosive.or.abra-

sive.gasses..

•. Air.stream.temperatures.between.120°F.(49°C).and.

-20°F.(-29°C).with.a.maximum.temperature.fluctua-

tion.of.15°F.(8°C).per.minute..

•. Ambient.temperatures.shall.not.exceed.104°F.(40°C).

for.standard.design.fans.

•. Constant.speed.operation.

Operating.a.fan.in.any.of.the.following.conditions.could.

cause.a.safety.hazard:

•. Do.not.operate.a.fan.in.an.environment.that.it.was.

not.designed.for..This.includes.operating.the.fan.in.

temperatures. or. with. abrasive. or. corrosive. vapors.

or. chemicals. or. solid. material. (including. fly. ash).

other.than.the.fan.was.designed.for..Operating.at.

elevated.temperatures.or.with.abrasive.or.corrosive.

vapors.requires.special.considerations.that.must.be.

incorporated.in.the.design,.material.selection,.coat-

ing,.and.maintenance.of.the.fan..

•. Do.not.operate.a.fan.at.a.higher.speed.than.the.

fan,. drives,. seals,. bearings,. or. other. components.

were.designed.for..

•. Do.not.use.variable.rotational.speed.service.without.

first.consulting.Twin.City.Fan.Companies,.Ltd.

•. Do.not.operate.a.fan.without.the.bearings.and.cou-

plings. properly. lubricated.. Lubrication. intervals. are.

explained.in.corresponding.maintenance.sections.of.

this.manual..

•. Do.not.operate.a.fan.exhibiting.increased.vibration.

levels..Filter.in.readings.should.be.7.2.mm/s.RMS.

or.less.

•. Do.not.operate.the.fan.in.stall.
•. Do.not.operate.the.fan.with.replacement.or.added.

components. that. are. not. recommended. by. Twin.

City. Fan. Companies,. Ltd.. The. use. of. insufficient.

components. could. cause. premature. wear. and.

failure..