beautypg.com

Carrier WEATHERMAKER 48AJ User Manual

Page 24

background image

24

Table 8A — Electrical Data — 48AJ,AK,AW,AY Units without Convenience Outlet (cont)

LEGEND

*Fuse or HACR circuit breaker per NEC.

NOTES:
1. In compliance with NEC requirements for multimotor and combination

load equipment (refer to NEC Articles 430 and 440), the overcurrent
protective device for the unit shall be fuse or HACR breaker. The
Canadian units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
Use the following formula to determine the percent
of voltage imbalance.
% Voltage imbalance

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the max-
imum allowable 2%.

UNIT

SIZE

48A

VOLTAGE

3 PH, 60 Hz

VOLTAGE

RANGE

COMPRESSOR

CONDENSER

FAN MOTOR

EVAPORATOR

FAN MOTOR

POWER

EXHAUST

POWER SUPPLY

Cir A, No. 1 Cir A, No. 2 Cir B, No. 1 Cir B, No. 2

Min Max

RLA

LRA

RLA

LRA

RLA

LRA

RLA

LRA

Qty

FLA

Hp

FLA

FLA (total)

MCA

MOCP*

051

208

187

229

34.3

265

34.3

265

34.3

265

34.3

265

6

6.5

(ea)

20

59.4

250.5

300

35.4

285.9

300

25

74.8

269.7

300

35.4

305.1

350

30

88

286.2

350

35.4

321.6

400

40

114

318.7

400

35.4

354.1

450

230

207

253

34.3

265

34.3

265

34.3

265

34.3

265

6

6.6

(ea)

20

54

244.3

250

35.4

279.7

300

25

68

261.8

300

35.4

297.2

350

30

80

276.8

350

35.4

312.2

350

40

104

306.8

400

35.4

342.2

400

460

414

508

16

120

16

120

16

120

16

120

6

3.3

(ea)

20

27

117.6

125

18.9

136.5

150

25

34

126.3

150

18.9

145.2

175

30

40

133.8

150

18.9

152.7

175

40

52

148.8

200

18.9

167.7

200

575

518

632

12.9

80

12.9

80

12.9

80

12.9

80

6

2.6

(ea)

20

22

94.7

110

14.4

109.1

125

25

27

101.0

125

14.4

115.4

125

30

32

107.2

125

14.4

121.6

150

40

41

118.5

150

14.4

132.9

150

060

208

187

229

40.8

265

47

380

40.8

265

47

380

6

6.5

(ea)

25

75.0

308.1

350

35.4

343.5

400

30

88.0

324.6

400

35.4

360.0

400

40

114.0

357.1

450

35.4

392.5

450

230

207

253

40.8

265

47

380

40.8

265

47

380

6

6.6

(ea)

25

68.0

300.2

350

35.4

335.6

350

30

80.0

315.2

350

35.4

350.6

400

40

104.0

345.2

400

35.4

380.6

450

460

414

508

20.2

135

22.4

175

20.2

135

22.4

175

6

3.3

(ea)

25

34.0

147.5

175

18.9

166.4

175

30

40.0

155.0

175

18.9

173.9

200

40

52.0

170.0

200

18.9

188.9

225

575

518

632

16.6

120

18.6

140

16.6

120

18.6

140

6

2.6

(ea)

25

27.0

119.8

125

18.9

138.7

150

30

32.0

126.0

150

18.9

144.9

175

40

41.0

137.3

175

18.9

156.2

175

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.

7
457