Table 8A — Electrical Data — 48AJ,AK,AW,AY Units without Convenience Outlet
See Legend and Notes on page 24.
UNIT
SIZE
48A
VOLTAGE
3 PH, 60 Hz
VOLTAGE
RANGE
COMPRESSOR
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
POWER
EXHAUST
POWER SUPPLY
Cir A, No. 1 Cir A, No. 2 Cir B, No. 1 Cir B, No. 2
Min Max
RLA
LRA
RLA
LRA
RLA
LRA
RLA
LRA
Qty
FLA
Hp
FLA
FLA (total)
MCA
MOCP*
020
208
187
229
23
184
23
184
23
184
—
—
2
6.5
(ea)
5
16.7
—
104.5
125
23.6
128.1
150
10
30.8
—
120.5
150
23.6
144.1
150
15
46.2
—
139.8
175
23.6
163.4
200
230
207
253
23
184
23
184
23
184
—
—
2
6.6
(ea)
5
15.2
—
103.2
125
23.6
126.8
150
10
28.0
—
117.2
125
23.6
140.8
150
15
42.0
—
134.7
175
23.6
158.3
200
460
414
508
10.2
90
10.2
90
10.2
90
—
—
2
3.3
(ea)
5
7.6
—
47.4
50
12.6
60.0
70
10
14.0
—
54.7
60
12.6
67.3
80
15
21.0
—
63.5
80
12.6
76.1
90
575
518
632
9
73
9
73
9
73
—
—
2
2.6
(ea)
5
6.1
—
40.6
50
9.6
50.2
60
10
11.0
—
46.0
50
9.6
55.6
60
15
17.0
—
53.5
70
9.6
63.1
80
025
208
187
229
21.8
184
25.6
190
25.6
190
—
—
2
6.5
(ea)
5
16.7
—
109.1
125
23.6
132.7
150
10
30.8
—
124.5
150
23.6
148.1
175
15
46.2
—
143.8
175
23.6
167.4
200
230
207
253
21.8
184
25.6
190
25.6
190
—
—
2
6.6
(ea)
5
15.2
—
107.8
125
23.6
131.4
150
10
28.0
—
121.2
125
23.6
144.8
150
15
42.0
—
138.7
175
23.6
162.3
200
460
414
508
11
90
13.5
95
13.5
95
—
—
2
3.3
(ea)
5
7.6
—
55.6
60
12.6
68.2
80
10
14.0
—
62.1
70
12.6
74.7
80
15
21.0
—
70.9
90
12.6
83.5
100
575
518
632
9
73
10.2
75
10.2
75
—
—
2
2.6
(ea)
5
6.1
—
43.3
50
9.6
52.9
60
10
11.0
—
48.4
50
9.6
58.0
60
15
17.0
—
55.9
70
9.6
65.5
80
027
208
187
229
25.6
190
25.6
190
25.6
190
—
—
2
6.5
(ea)
10
30.8
—
128.3
150
23.6
151.9
175
15
46.2
—
147.6
175
23.6
171.2
200
20
59.4
—
164.1
200
23.6
187.7
225
230
207
253
25.6
190
25.6
190
25.6
190
—
—
2
6.6
(ea)
10
28.0
—
125.0
150
23.6
148.6
175
15
42.0
—
142.5
175
23.6
166.1
200
20
54.0
—
157.5
200
23.6
181.1
225
460
414
508
13.5
95
13.5
95
13.5
95
—
—
2
3.3
(ea)
10
14.0
—
64.6
70
12.6
77.2
90
15
21.0
—
73.4
90
12.6
86.0
100
20
27.0
—
80.9
100
12.6
93.5
110
575
518
632
10.2
75
10.2
75
10.2
75
—
—
2
2.6
(ea)
10
11.0
—
49.6
60
12.6
62.6
70
15
17.0
—
57.1
70
12.6
69.7
80
20
22.0
—
63.3
80
12.6
75.9
90